beautypg.com

Electrical connections, Safety precautions, Power supply m12 – Burkert Type 8645 User Manual

Page 80: Safety precautions power supply m12, Configuration and function of the modules english

background image

80 - 8645

ConfiGuraTion anD funCTion of The moDules

English

Electrical connections

Safety Precautions

cAuTION!

The system is live. Interventions may result in an acute risk of injury.
Always switch off the power supply before starting work!
Observe all applicable accident prevention and safety regulations for electrical equipment.

Power supply M12

The 4-pin round plug for the power supply has the following pin assignment:

Electronics

Inputs

Outputs

24 V DC (1) Outputs

24 V DC (2)
Logic

GND ()
Logic

GND (4) Outputs

PIN 1
+24 V
driver (Outputs)

PIN 4
GND
driver

PIN 2

+24 V

Logic

PIN

GND

Logic

Illustration: Power supply M12 - Intermediate module (Inside Module)

NOTE!

• Protect pin 1 of the power supply with a 4 A (medium time-lag) fuse and pin 2 with a 1

A (medium time-lag) fuse.

• In order to ensure the electromagnetic compatibility (EMC), connect screw terminal

FE (functional earthing) to earth potential with the shortest possible cable (0 cm).