Configuration and function of the modules english – Burkert Type 8645 User Manual
Page 73
ConfiGuraTion anD funCTion of The moDules
English
8645 - 7
Object
class
Instance
Attri-
butes
Ac-
cess
Length
byte
Area
Default Short Description
Report
outputs
150
1
Get/
Set
1
0 or 1
0
Turn on/off output
reports (short circuit
or non-present OUT)
0: Activate output
reports
1 : Deactivate output
reports
Filter inputs
150
1
4
Get/
Set
1
0 or 1
0
Input filter
1: Filter OFF
0: Filter ON
Write
EEPROM
150
1
5
Set
1
1 to
Data can be written
into EEPROM with
this object.
1: Actual module list
is written in EEPROM.
After power-up, it
becomes the Target
module list.
2: As valuje 1, but
here, at the end, a
Diag Byte with the
generated data will be
sent.
: Object Error action,
value, filter input and
reports output are
written into EEPROM.
Diagnose
Error type
and number
151
1
1
Get
1
Error type (MSB 4
Bit) and error number
(LSB 4 Bit) as per
LED display, Byte can
be transferred
cyclically.
Short-circuit
channel,
bus head
151
1
2
Get
1
1 diagnosis bit per 2
bus head outlets.
RIO/ZM
151
1
Get
1
Diagnosis of a RIO/
ZM,
address of a RIO or
ZM, which has a Diag;
MSB shows whether
ZM (0) or RIO (1)
Channel
short circuit
RIO/ZM
151
1
4
Get
1
1 diagnosis bit per 2
RIO/ZM outlets
The effected RIO/ZM
module is shown in
object 151/1/.
Discrete Output
Value
9
1 to 16
Get/
Set
2
0x0000
to
0xFFFF
0x0000 Valve value