beautypg.com

Operating and display elements, Rotary encoder switch – address and baud rate, Led-status displays – Burkert Type 8645 User Manual

Page 69: Operating� and display elements, Configuration and function of the modules english

background image

ConfiGuraTion anD funCTion of The moDules

English

8645 - 69

Operating� and display Elements

Rotary Encoder Switch – Address and Baud rate

(x10)

(x1)

Baud rate

Location: The rotary encoder switch is located in the lower part
of the DeviceNet fieldbus module (see illustration

Rotary Encoder

Switch).
Address setting:

Addresse 1 0 (x10) + 1 (x1)

: : :

Addresse 6 6 (x10) + (x1)

baud rate:

Value

Baud rate

0

125 kBaud

1

250 kBaud

2

500 kBaud

Illustration: Rotary encoder switch

LEd-Status displays

BUS_OK (BO)

FAILURE_SELECT (FS)

U_LOGIK_OK (U

l

)

U_SENSOR_OK (U

S

)

BUS_FAULT (BF)

FAILURE_NUMBER (FN)

U_DRIVER_OK (U

O

)

Display during
normal operations

BUS (BO)
BUS (BF)
FS
FN
U

o

U

i

U

S

ON
OFF
OFF
OFF
ON
ON
ON

Illustration: Allocation of the LED’s on the Field bus module DeviceNet

LED Status Displays

Abbreviation color

Meaning

Explanation

BO

green

BUS STATUS

See condition of the BUS STATUS LEDs

BF

red

BUS STATUS

See condition of the BUS STATUS-LEDs

FS

yello

FAILURE
SELECT

Defines the function of the LED FN:
FS lit: FN indicates the type of failure
FS not lit: FN indicates the failure number

FN

red

FAILURE
NUMBER

The number of flashing pulses indicates the failure type or fai-
lure number, depending on if FS is lit or not.

U

i

green

U Logik OK

Voltage for logic supply,
Inputs and bus interface provided.

U

O

green

U

DRIVER

OK

Power supply for the outputs available.

U

S

green

U Sensor OK

Separate display of the voltage for the inputs.