Fieldbus module profibus, Configuration and function, Technical data – Burkert Type 8645 User Manual
Page 29: General technical data, Fieldbus module profibus profibus, Config�uration and function, Configuration and function of the modules english
ConfiGuraTion anD funCTion of The moDules
English
8645 - 29
FIELdBuS MOduLE PROFIBuS
PROFIBuS
®
config�uration and Function
The fieldbus module connects the FreeLINE automation
system to a fieldbus network. The module is used for digital
networking with the higher level control system.
Illustration: Fieldbus module PROFIBUS
PROFIBUS
®
Technical data
General Technical data
Operating voltage
24 V -15 % / +20 %
Residual ripple
2 Vss
Current consumption
Inputs / logic
Outputs
max. 1 A
max. 4 A (M12)
PROFIBUS
®
transmission rate
Inductances in the module
9.6 kBaud to 12 MBaud
100 nH / 0.16 Ohm for incoming and outgoing bus
Electrical connections
Power supply
PROFIBUS
®
incoming
PROFIBUS
®
outgoing
RIO
Address setting
Address range
Diagnostics
Integrated diagnostic
interface
Diagnostic LEDs
M12, plug, 4-pin, max. 4 A
M12, plug, 5-pin, b-coded
M12, jack, 5-pin, b-coded
M8, jack, 4-pin
via rotary encoder switch
0 to 99
-pin (RM 2.54)
2 x bus status, 2 x error indication, x supply voltage
Pneumatic connections
Compressed air supply
Exhaust air
Auxiliary control air
Pilot control exhaust air
G 1/4”, NPT 1/4”, D10
G 1/4”, NPT 1/4”, D10
M5, D6, D4, D 1/4”
M5, D6, D4, D 1/4”
Possibility of expansion in the
system
up to 49 RIO-participants
Material
PBT
Weight
50 g