Troubleshooting, Bus error, Global control operate only – Burkert Type 8645 User Manual
Page 35: Configuration and function of the modules english
ConfiGuraTion anD funCTion of The moDules
English
8645 - 5
Troubleshooting�
Bus Error
LED
Status
Description
cause of Error
BUS (BO)
OFF
Response monitoring time on
FreeLINE has expired.
The master has not responded.
During commissioning:
Check network configuration at master
(controller) and station address of the
valve cluster.
During operations:
Check master (controller) and bus
cable.
BUS (BF)
ON
FS
OFF
FN
OFF
U
i
ON
U
O
ON
U
S
ON
Global control Operate only
LED
Status
Description
cause of Error
BUS (BO)
OFF
The fieldbus module is ready for the
status “Data Exchange”, but the
master sends no Global Control
Operate telegram [e.g. if the PLC is at
Stop (Global Control Clear)].
This status does not represent an
error. The function can, however, be
bypassed in the parameter telegram
(see chapter
Commissioning).