beautypg.com

Operating and display elements, Rotary encoder switch - address and baud rate, Led status displays – Burkert Type 8645 User Manual

Page 44: Operating� and display elements, Configuration and function of the modules english

background image

44 - 8645

ConfiGuraTion anD funCTion of The moDules

English

Operating� and display Elements

Rotary Encoder Switch - Address and Baud rate

(x10)

(x1)

baud rate

Location: The rotary encoder switch is located in the lower part
of the CANopen fieldbus module (see illlustration

Rotary encoder

switch).
Address setting: Address 1 0 (x10) + 1 (x1)
: : :
Address 99 9 (x10) + 9 (x1)

baud rate:

Value baud rate

Value Baud rate

0

1 Mbaud

4

125 kbaud

1

800 kbaud

5

100 kbaud

2

500 kbaud

6

50 kbaud

250 kbaud

7

20 kbaud

Illustration: Rotary encoder switch

LEd Status displays

BUS_OK (BO)

FAILURE_SELECT (FS)

U_LOGIC_OK (U

l

)

U_SENSOR_OK (U

S

)

BUS_FAULT (BF)

FAILURE_NUMBER (FN)

U_DRIVER_OK (U

O

)

Display during nor-
mal operation

BUS (BO)
BUS (BF)
FS
FN
U

o

U

i

U

S

ON
OFF
OFF
OFF
ON
ON
ON

Illustration: Allocation of the LEDs on the Fieldbus module CANopen

LED Status Displays

Abbreviation color

Meaning

Explanation

BO

green

Bus OK

see table

CANopen RUN LED

BF

red

Bus FAULT

see table

CANopen ERROR LED

FS

yellow

FAILURE
SELECT

Defines the function of the LED FN:
FS lit: FN indicates the type of failure
FS not lit: FN indicates the failure number

FN

red

FAILURE
NUMBER

The number of flashing pulses indicates the failure type or failure
number, depending on the setting of FS.

U

i

green

U Logic OK

Voltage for logic supply,
Inputs and bus interface provided.

U

O

green

U Driver OK

Power supply for the outputs OK.

U

S

green

U Driver OK

Separate display of the voltage for the inputs.