44 - 8645
ConfiGuraTion anD funCTion of The moDules
English
Operating� and display Elements
Rotary Encoder Switch - Address and Baud rate
(x10)
(x1)
baud rate
Location: The rotary encoder switch is located in the lower part
of the CANopen fieldbus module (see illlustration
Rotary encoder
switch).
Address setting: Address 1 0 (x10) + 1 (x1)
: : :
Address 99 9 (x10) + 9 (x1)
baud rate:
Value baud rate
Value Baud rate
0
1 Mbaud
4
125 kbaud
1
800 kbaud
5
100 kbaud
2
500 kbaud
6
50 kbaud
250 kbaud
7
20 kbaud
Illustration: Rotary encoder switch
LEd Status displays
BUS_OK (BO)
FAILURE_SELECT (FS)
U_LOGIC_OK (U
l
)
U_SENSOR_OK (U
S
)
BUS_FAULT (BF)
FAILURE_NUMBER (FN)
U_DRIVER_OK (U
O
)
Display during nor-
mal operation
BUS (BO)
BUS (BF)
FS
FN
U
o
U
i
U
S
ON
OFF
OFF
OFF
ON
ON
ON
Illustration: Allocation of the LEDs on the Fieldbus module CANopen
LED Status Displays
Abbreviation color
Meaning
Explanation
BO
green
Bus OK
see table
CANopen RUN LED
BF
red
Bus FAULT
see table
CANopen ERROR LED
FS
yellow
FAILURE
SELECT
Defines the function of the LED FN:
FS lit: FN indicates the type of failure
FS not lit: FN indicates the failure number
FN
red
FAILURE
NUMBER
The number of flashing pulses indicates the failure type or failure
number, depending on the setting of FS.
U
i
green
U Logic OK
Voltage for logic supply,
Inputs and bus interface provided.
U
O
green
U Driver OK
Power supply for the outputs OK.
U
S
green
U Driver OK
Separate display of the voltage for the inputs.