Combination modules, Configuration and function, Technical data – Burkert Type 8645 User Manual
Page 88: General technical data, Config�uration and function, Configuration and function of the modules english
88 - 8645
ConfiGuraTion anD funCTion of The moDules
English
cOMBINATION MOduLES
config�uration and Function
The combination module performs both pneumatic and
electrical functions.
Two valves from each of types 6524, 6525 or 0460 are
integrated into the module; the electrical indicators are
located on the top.
Illustration: Combination modules
Technical data
General Technical data
Supply voltage (transmitters)
24 V -15 % / +20 %
Supply current (transmitters)
max. 700 mA (in the system)
Current consumption per valve function
(at 24 V)
on pick-up (≤120 ms)
lowered
≤60 mA
≤25 mA
Connections
Electrical
Pneumatic
4 x M8 (-pin), jack
2 x M12 (4-pin), double allocation, jack
D4, D6, D 1/4”
Inputs
Logic level high
Logic level low
1 to 0 V
0 to 5 V
Input delay in conjunction with fieldbus
module
typ. 4 ms
Displays
4 LEDs for the status of the feedback
4 (2) LEDs for switching status of the valves
Sensor types
2- / -conductor (pnp)
Material
PBT
Weight
with /2 or 5/2-way valves
with 2 x /2-way valves
27 g
0 g