beautypg.com

Combination modules, Configuration and function, Technical data – Burkert Type 8645 User Manual

Page 88: General technical data, Config�uration and function, Configuration and function of the modules english

background image

88 - 8645

ConfiGuraTion anD funCTion of The moDules

English

cOMBINATION MOduLES

config�uration and Function

The combination module performs both pneumatic and
electrical functions.
Two valves from each of types 6524, 6525 or 0460 are
integrated into the module; the electrical indicators are
located on the top.

Illustration: Combination modules

Technical data

General Technical data

Supply voltage (transmitters)

24 V -15 % / +20 %

Supply current (transmitters)

max. 700 mA (in the system)

Current consumption per valve function
(at 24 V)
on pick-up (≤120 ms)
lowered


≤60 mA

≤25 mA

Connections
Electrical

Pneumatic


4 x M8 (-pin), jack
2 x M12 (4-pin), double allocation, jack
D4, D6, D 1/4”

Inputs
Logic level high
Logic level low


1 to 0 V
0 to 5 V

Input delay in conjunction with fieldbus
module

typ. 4 ms

Displays

4 LEDs for the status of the feedback
4 (2) LEDs for switching status of the valves

Sensor types

2- / -conductor (pnp)

Material

PBT

Weight
with /2 or 5/2-way valves
with 2 x /2-way valves


27 g
0 g