Commissioning english – Burkert Type 8645 User Manual
Page 126
126 - 8645
CommissioninG
English
Examples for hardware configuration and explanation of the different module types
Illustration: Example of maximum configuration with 16 IN / 16 OUT
Pull the main/inside module DI16/DO16 into the slave, Type 8645/MK01 (drag and drop).
Combination module
4PO / 4DI
Type 8645 / MK01
Combination module
4PO / 4DI
Combination module
4PO / 4DI
Combination module
4PO / 4DI
Termination module
Illustration: Example of maximum configuration with 16 IN / 16 OUT (with combination modules 4PO/4DI)
Module types
Main/Inside DI16/DO16
Main module/intermediate module: 2 byte inputs , 2 byte outputs
Main/Inside DI8/DO8
Main module/intermediate module: 1 byte inputs , 1 byte outputs
Main/Inside only DI8
Main module/intermediate module: 1 byte inputs
Main/Inside only DO8
Main module/intermediate module: 1 byte outputs
Add-on DI8
Expansion module: 1 byte inputs
Add-on DO8
Expansion module: 1 byte outputs
A main inside module must be used for each hardware configuration. Empty slots upt to 2 buytes IN or 2 bytes
OUT can be filled with the add-on modules.
In the above example, a 2 byte IN / 2 byte OUT module was used. The inputs occupy the EB 1 and 2, the
outputs the AB and 4.