The following mask appears:
Illustration: Parameterisation of the slave - object properties
Explanation of the device-specific paramters
parameters
Explanation
Data Exchange Mode
Without Global Control-Operate
Activate / deactivate Global Control Operate
On Global Control-Operate only
In order to enter Data Exchange mode, the master must transmit a Glo-
bal Control Operate. Otherwise, the BUS (BF) LED flashes
(e. g.if the PLC is at stop).
Short circuit detection
Short circuit detection
With Short circuit detection
Short circuits on the digital outputs and non-existent driven outputs are
detected. Incorrect messages can be output, however, in the event of
capacitive loads.
Without Short circuit detection
Short circuits on the digital outputs and non-existent driven outputs are
not detected.
Input filter
Input filter
Input filter ON
Only signals with a length >4 ms are detected on the feedback inputs.
Incorrect messages due to ESD are thus avoided.
Input filter OFF
Signals with a length of <4 ms are also detected on the feedback in-
puts. Incorrect messages may therefore be transmitted when using M8
plugs (without plastic insert) due to ESD.