To expand the system with an intermediate module (expansion by 16 DI/16 DO), proceed as follows:
Drag a further Main/Inside DI16/DO16“ module into the slave Type 8645/MK01 (drag and drop).
The same module types are available as already described for the commissioning of the Profibus
®
field bus
module.
Module types
Main/Inside DI16/DO16
Main module/intermediate module: 2 byte inputs , 2 byte outputs
Main/Inside DI8/DO8
Main module/intermediate module: 1 byte inputs , 1 byte outputs
Main/Inside only DI8
Main module/intermediate module: 1 byte inputs
Main/Inside only DO8
Main module/intermediate module: 1 byte outputs
Add-on DI8
Expansion module: 1 byte inputs
Add-on DO8
Expansion module: 1 byte outputs
A main/inside module must be used for each hardware configuration. Empty slots up to 2 bytes IN or 2 bytes
OUT can be filled with the add-on modules.
Different examples of hardware configuratons
Illustration: Example of configuration with 16 IN/16 OUT (Main module); 8 IN/8OUT (Intermediate module)
Illustration: Example of configuration with 8 IN/8 OUT (Main module); 8 IN/8 OUT (Intermediate module) each with
add-on DO8 and DI8
Through this configuration (with add-on DO8 and DI8) you have the possibility of freely assigning the addres-
ses for the output and input bytes. This is not possible with the main/inside DI16/DO16 module.The second
byte is automatically one address higher than the first byte.
Parameterisation of the individual modules
For parameterisation of a module, proceed as described in chapter
Commissioning / Fieldbus Module
Profibus
®
.