ConfiGuraTion anD funCTion of The moDules

English

8645 - 85

Electrical connections

Safety Precautions

cAuTION!

The system is live. Interventions may result in an acute risk of injury.
Always switch off the power supply before starting work!
Observe all applicable accident prevention and safety regulations for electrical equipment.

Power supply M12

The 4-pin round plug for the power supply has the following pin assignment:

Electronics

Inputs

Outputs

24 V DC (1) Outputs

24 V DC (2)
Logic

GND ()
Logic

GND (4) Outputs

PIN 1
+24 V
driver (Outputs)

PIN 4
GND
driver

PIN 2

+24 V

Logic

PIN

GND

Logic

Illustration: Power supply M12 - RIO Module

NOTE!

• Protect pin 1 of the power supply with a 4 A (medium time-lag) fuse and pin 2 with

a 1 A (medium time-lag) fuse.

• In order to ensure the electromagnetic compatibility (EMC), connect screw terminal

FE (functional earthing) to earth potential with the shortest possible cable (0 cm).

RIO Bus connection M8

The M8 plug system is used for the RIO bus connection. The assignment is described below.

pin No.

Signal

Relevance

1

CAN_H

High signal CAN communication

2

CAN_L

Low signal CAN communication

Screen

Screen or protective earth

4

--

--

NOTE!

The maximum length of the line between two RIO modules must not exceed 0 m.
The total length of the RIO bus must not exceed 500 m.