Electrical connections, Safety precautions, Power supply m12 – Burkert Type 8645 User Manual
Page 85: Rio bus connection m8, Configuration and function of the modules english
ConfiGuraTion anD funCTion of The moDules
English
8645 - 85
Electrical connections
Safety Precautions
cAuTION!
The system is live. Interventions may result in an acute risk of injury.
Always switch off the power supply before starting work!
Observe all applicable accident prevention and safety regulations for electrical equipment.
Power supply M12
The 4-pin round plug for the power supply has the following pin assignment:
Electronics
Inputs
Outputs
24 V DC (1) Outputs
24 V DC (2)
Logic
GND ()
Logic
GND (4) Outputs
PIN 1
+24 V
driver (Outputs)
PIN 4
GND
driver
PIN 2
+24 V
Logic
PIN
GND
Logic
Illustration: Power supply M12 - RIO Module
NOTE!
• Protect pin 1 of the power supply with a 4 A (medium time-lag) fuse and pin 2 with
a 1 A (medium time-lag) fuse.
• In order to ensure the electromagnetic compatibility (EMC), connect screw terminal
FE (functional earthing) to earth potential with the shortest possible cable (0 cm).
RIO Bus connection M8
The M8 plug system is used for the RIO bus connection. The assignment is described below.
pin No.
Signal
Relevance
1
CAN_H
High signal CAN communication
2
CAN_L
Low signal CAN communication
Screen
Screen or protective earth
4
--
--
NOTE!
The maximum length of the line between two RIO modules must not exceed 0 m.
The total length of the RIO bus must not exceed 500 m.