Lost ok to fill alarm/fast fill, Lost ok to fill alarm/slow fill, Fast fill gate did not open alarm – Hardy HI 3010 Filler/Dispenser Controller User Manual

Page 102: Resume filling fast display, Fast gate did not close

background image

HI-3010 Filler/Dispenser/IBC

86

Service Manual

Alarm. The Filler/Dispenser begins
filling.

NOTE:

The OK to Fill Timer has a preset time to deter-
mine if it is OK to Fill. If the OK to Fill times out,
it means that the preset time is too short for the
process and the NOT OK to FILL Alarm appears
with no real alarm conditions. You may need to
reset the timer if it appears that no electrical or
mechanical reason for the alarm is determined.
The OK to FILL timer may be set incorrectly for
your process. See the HI 3010 Service Manual for
Instructions on setting the OK to FILL Timer.

Lost OK to Fill Alarm

- - - - - ALARM CONDITION - - - - -

During the filling process, conditions may develop that
cause the Filler/Dispenser to lose the OK to FILL during
Fast Fill or Slow Fill. When this occurs an alarm appears that
says LOST OK TO FILL. (See Figs. 7-2 & 7-3)

FIG. 7-2 LOST OK TO FILL ALARM/FAST FILL

FIG. 7-3 LOST OK TO FILL ALARM/SLOW FILL

1.

The Operator needs to determine why
the system LOST OK to FILL by
checking for problems with the elec-
trical and /or mechanical systems.

2.

Once the problem has been fixed,
push the Clear button to clear the
Alarm. Press the Start button, the
Filler/Dispenser resumes filling from
where it stopped. Press Stop to Halt.

Fast Gate Did Not Open Alarm

- - - - - ALARM CONDITION - - - - -

If the Fast Fill Gate is not open at the time
you want to fill, the FAST GATE DID
NOT OPEN alarm appears on the display.
(See Fig. 7-4)

FIG. 7-4 FAST FILL GATE DID NOT OPEN ALARM

1.

Determine why the Fast Fill Gate did
not open and correct the problem.

2.

Press the Clear button to clear the
alarm. The RESUME FILLING FAST
display appears. (See Fig. 7-5)

FIG. 7-5 RESUME FILLING FAST DISPLAY

3.

Press the Start button to resume fast
fill.

Fast Gate Did Not Close Alarm

- - - - - ALARM CONDITION - - - - -

If the Fast Fill Gate does not close at the
end of a fill, the FAST GATE DID NOT
CLOSE alarm appears on the display. (See
Fig. 7-6)

FIG. 7-6 FAST GATE DID NOT CLOSE