Yaskawa AC Drive P1000 Bypass Technical Manual User Manual
Page 94

n
b5-01: PID Mode
Enables or disables the PID operation and selects the PID operation mode.
No.
Parameter Name
Setting Range
Default
b5-01
PID Mode
0, 1
0
Setting 0: PID Disabled
Setting 1: Enabled D = Feedback
n
b5-02: Proportional Gain Setting (P)
Sets the P gain applied to the PID input. Larger values will tend to reduce the error but may cause oscillations if set too high,
while lower values may allow too much offset between the setpoint and feedback.
No.
Name
Setting Range
Default
b5-02
Proportional Gain Setting (P)
0.00 to 25.00
1.00
n
b5-03: Integral Time Setting (I)
Sets the time constant used to calculate the integral of the PID input. The shorter the integral time set to b5-03, the faster the
offset will be eliminated. If the integral time is set too short, however, overshoot or oscillation may occur. To turn off the
integral time, set b5-03 to 0.00.
No.
Name
Setting Range
Default
b5-03
Integral Time Setting (I)
0.0 to 360.0 s
1.0 s
n
b5-04: Integral Limit Setting
Sets the maximum output possible from the integral block as a percentage of the maximum frequency (E1-04).
No.
Name
Setting Range
Default
b5-04
Integral Limit Setting
0.0 to 100.0%
100.0%
Note:
On some applications, especially those with rapidly varying loads, the output of the PID function may show a fair amount of oscillation.
Program b5-04 to apply a limit to the integral output and suppress this oscillation.
n
b5-05: Derivative Time (D)
Sets the time the drive predicts the PID input/PID feedback signal based on the derivative of the PID input/PID feedback.
Longer time settings improve the response but can cause vibrations, while shorter time settings reduce the overshoot but reduce
controller responsiveness. D control is disabled by setting b5-05 to zero seconds.
No.
Name
Setting Range
Default
b5-05
Derivative Time (D)
0.00 to 10.00 s
0.00 s
n
b5-06: PID Output Limit
Sets the maximum output possible from the entire PID controller as a percentage of the maximum frequency (E1-04).
No.
Name
Setting Range
Default
b5-06
PID Output Limit
0.0 to 100.0%
100.0%
n
b5-07: PID Offset Adjustment
Sets the offset added to the PID controller output as a percentage of the maximum frequency (E1-04).
No.
Name
Setting Range
Default
b5-07
PID Offset Adjustment
-100.0 to 100.0%
0.0%
n
b5-08: PID Primary Delay Time Constant
Sets the time constant for the filter applied to the output of the PID controller. Normally, change is not required.
5.2 b: Application
94