beautypg.com

Yaskawa AC Drive P1000 Bypass Technical Manual User Manual

Page 189

background image

The output current has fallen below the motor

underload curve defined in L6-14 for longer than

the time set to L6-03

Adjust the value set to L6-14 so that output current remains above the motor underload curve during

normal operation.

HOA Keypad Display

Fault Name

Uv1

DC Bus Undervoltage
Voltage in the DC bus fell below the undervoltage detection level (L2-05).
• For 208 V Bypass Drives: approximately 190 V
• For 480 V Bypass Drives: approximately 440 V
The fault is output only if L2-01 is set to 0 or 1 and the DC bus voltage has fallen below the level set
to L2-05 for longer than the time set to L2-02

<1>

.

Cause

Possible Solution

Input power phase loss

• The main circuit drive input power is wired incorrectly.
• Correct the wiring.

One of the drive input power wiring terminals is

loose

• Ensure there are no loose terminals.
• Apply the tightening torque specified in this manual to fasten the terminals.

Refer to Wire Gauge

and Tightening Torque Specifications on page 43

for details.

There is a problem with the voltage from the drive

input power

• Check the voltage.
• Correct the voltage to be within the range listed in drive input power specifications.
• If there is no problem with the power supply to the main circuit, check for problems with the main

circuit magnetic contactor.

The power has been interrupted

Correct the drive input power.

The main circuit capacitors are worn

• Check the maintenance time for the capacitors (U4-05).
• Replace either the control board or the entire drive if U4-05 exceeds 90%. For instructions on

replacing the control board, contact Yaskawa or a Yaskawa representative.

The relay or contactor on the soft-charge bypass

circuit is damaged

• Cycle power to the drive and see if the fault reoccurs.
• If the problem continues, replace either the control board or the entire drive. For instructions on

replacing the control board, contact Yaskawa or a Yaskawa representative.

• Check monitor U4-06 for the performance life of the soft-charge bypass.
• Replace either the control board or the entire drive if U4-06 exceeds 90%. For instructions on

replacing the control board, contact Yaskawa or a Yaskawa representative.

<1> Details on this function can be found in the standard P1000 Technical Manual (SIEPYAIP1U01) at www.yaskawa.com.

HOA Keypad Display

Fault Name

Uv2

Control Power Supply Voltage Fault
Voltage is too low for the control drive input power.

Cause

Possible Solution

Internal circuitry is damaged

• Cycle power to the drive. Check if the fault reoccurs.
• If the problem continues, replace either the control board or the entire drive. For instructions on

replacing the control board, contact Yaskawa or a Yaskawa representative.

HOA Keypad Display

Fault Name

Uv3

Undervoltage 3 (Soft-Charge Circuit Fault)
The soft-charge bypass circuit failed.

Cause

Possible Solution

The relay or contactor on the soft-charge bypass

circuit is damaged

• Cycle power to the drive and see if the fault reoccurs.
• If the problem continues, replace either the control board or the entire drive. For instructions on

replacing the control board, contact Yaskawa or a Yaskawa representative.

• Check monitor U4-06 for the performance life of the soft-charge bypass.
• Replace either the control board or the entire drive if U4-06 exceeds 90%. For instructions on

replacing the control board, contact Yaskawa or a Yaskawa representative.

HOA Keypad Display

Fault Name

voF

Output Voltage Detection Fault
Problem detected with the voltage on the output side of the drive.

Cause

Possible Solution

Hardware is damaged

Replace the control board or the entire drive. For instructions on replacing the control board, contact

Yaskawa or a Yaskawa representative.

6.4 Fault Detection

YASKAWA SIEP YAIP1B 01A YASKAWA AC Drive – P1000 Bypass Technical Manual

189

6

Diagnostics & Troubleshooting