B.15 defaults by drive model – Yaskawa AC Drive P1000 Bypass Technical Manual User Manual
Page 277
No.
Name
Unit
Default Settings
–
Drive Model
–
2A0040
2A0056
2A0069
2A0081
Bypass Model
D030
D046
D059
D074
o2-04
Drive Model Selection
Hex.
6B
6D
6E
6F
E2-11
Motor Rated Power
kW
(HP)
11
(15)
15
(20)
18.5
(25)
22
(30)
b3-04
V/f Gain during Speed Search
%
100
100
100
100
b3-06
Output Current 1 during Speed Search
–
0.5
0.5
0.5
0.5
b3-07
Output Current 2 during Speed Search
(Speed Estimation Type)
–
–
–
–
–
b3-26
Start Speed Search Select
–
–
–
–
–
b8-03
Energy Saving Control Filter Time Constant
s
0.50
0.50
0.50
0.50
b8-04
Energy Saving Coefficient Value
–
70.44
63.13
57.87
51.79
C5-17
Motor Inertia
kgm
2
0.053
0.076
0.138
0.165
C6-02
Carrier Frequency Selection
–
7
7
7
7
E2-01
Motor Rated Current
A
39.7
53
65.8
77.2
E2-02
Motor Rated Slip
Hz
1.7
1.6
1.67
1.7
E2-03
Motor No-Load Current
A
11.2
15.2
15.7
18.5
E2-05
Motor Line-to-Line Resistance
Ω
0.23
0.138
0.101
0.079
E2-06
Motor Leakage Inductance
%
19.5
17.2
15.7
19.5
E2-10
Motor Iron Loss for Torque Compensation
W
245
272
505
538
L2-02
Momentary Power Loss Ride-Thru Time
s
1
2
2
2
L2-03
Momentary Power Loss Minimum Baseblock Time
s
0.9
1
1
1
L2-04
Momentary Power Loss Voltage Recovery Time
s
0.3
0.6
0.6
0.6
L3-24
Motor Acceleration Time for Inertia Calculations
s
0.265
0.244
0.317
0.355
L8-02
Overheat Alarm Level
°C
125
120
120
125
L8-35
Installation Method Selection
–
2
2
2
2
L8-38
Carrier Frequency Reduction Selection
–
2
2
2
2
n1-03
Hunting Prevention Time Constant
ms
10
10
10
10
B.15 Defaults by Drive Model
YASKAWA SIEP YAIP1B 01A YASKAWA AC Drive – P1000 Bypass Technical Manual
277
B
Parameter List