Drive derating data, Rated current depending on carrier frequency, A.4 drive derating data – Yaskawa AC Drive P1000 Bypass Technical Manual User Manual
Page 231

A.4 Drive Derating Data
The drive can be operated at above the rated temperature, altitude, and default carrier frequency by derating the drive capacity.
u
Rated Current Depending on Carrier Frequency
The tables below show the drive output current depending on the carrier frequency settings.
The 2 kHz values shown for ND below are equal to the drive rated current shown on the drive nameplate. Increasing the carrier
frequency above 2 kHz will reduce the ND rated output current of the drive.
Table A.10 Three-Phase 208 Vac Bypass Drive Carrier Frequency and Current Derating
Three-Phase 208 Vac Bypass Drives
Drive Model
Rated Current [A]
Normal Duty Rating (ND)
2 kHz
8 kHz
15 kHz
2A0004
3.5
3.2
2.56
2A0006
6
5
4
2A0008
8
6.9
5.5
2A0010
9.6
8
6.4
2A0012
12
11
8.8
2A0018
17.5
14
11.2
2A0021
21
17.5
14
2A0030
30
25
20
2A0040
40
33
26.4
2A0056
56
47
37.6
2A0069
69
60
48
2A0081
81
75
53
2A0110
110
85
60
2A0138
138
115
81
Three-Phase 208 Vac Bypass Drives
Drive Model
Rated Current [A]
Normal Duty Rating (ND)
2 kHz
5 kHz
10 kHz
2A0169
169
145
116
2A0211
211
180
144
2A0250
250
215
172
2A0312
312
283
226
2A0360
360
346
277
2A0415
415
415
332
Table A.11 Three-Phase 480 Vac Bypass Drive Carrier Frequency and Current Derating
Three-Phase 480 Vac Bypass Drives
Drive Model
Rated Current [A]
Normal Duty Rating (ND)
2 kHz
8 kHz
15 kHz
4A0002
2.1
1.8
1.1
4A0004
4.1
3.4
2
4A0005
5.4
4.8
2.9
4A0007
6.9
5.5
3.3
4A0009
8.8
7.2
4.3
4A0011
11.1
9.2
5.5
4A0018
17.5
14.8
8.9
A.4 Drive Derating Data
YASKAWA SIEP YAIP1B 01A YASKAWA AC Drive – P1000 Bypass Technical Manual
231
A
Specifications