beautypg.com

Bypass operations by n2, Observing the bypass operation, Controlling the bypass – Yaskawa AC Drive P1000 Bypass Technical Manual User Manual

Page 361: G.4 bypass operations by n2

background image

G.4 Bypass Operations by N2

The drive operations that can be performed by N2 communication depend on drive parameter settings. This section explains

the functions that can be used and related parameter settings.

u

Observing the Bypass Operation

A controller can perform the following actions with N2 communications at any time regardless of parameter settings (except

for Z3-oo parameters):
• Observe drive status and drive control terminal status from a controller
• Read and write parameters
• Set and reset faults
• Set multi-function inputs.

Note:

Input settings from the input terminals So and from N2 communications are both linked by a logical OR operation.

u

Controlling the Bypass

Select an external reference and adjust the parameters in

Table C.1

accordingly to start and stop the drive or set the frequency

reference using BACnet communications.

Table G.1 Setting Parameters for Drive Control from BACnet

Reference Source

Parameter

Name

Required Setting

External Reference 1

Z1-07

Frequency Reference Select

2

Z1-08

Run Command Select

2

Refer to Z1-07: Speed Reference Select on page 152

and

Refer to Z1-08: Run Command Select on page 153

for details on

external reference parameter selections.

n

Bypass Functions

Each of the following functions must be enabled during start-up:

Start and Stop the Bypass

Set the Run Forward Command (BO 1) to run the in the forward direction. Set the Run Reverse Command (BO 2) to run the

in the reverse direction. Run/Stop Monitor (BI 1) shows the current run status. Forward/Reverse Monitor (BI 2) shows the

current direction.

NOTICE: Damage to Equipment. Improper motor direction may damage equipment if parameter b1-04, Reverse Enable, is set to 0 (Enable).

Lock the Bypass Panel

This function is not supported in the P1000 Bypass.

Digital Inputs

Multi-Function Input S3 (BO 5) through Multi-Function Input S7 (BO 9) are physical digital inputs on the bypass. They can

be set either by external devices, such as limit or pressure switches, or by the network. Their function depends on how the

bypass has been programmed. The multi-function input status can be monitored through Multi-Function Input 3 Monitor (BI

15) through Multi-Function Input 7 Monitor (BI 19). The Multi-Function Input # Monitor state is the logical OR of the serial

command value (BO 5 through BO 9) and the state of the external connection.

Note:

The multi-function inputs can be set by both external devices or over the network. Use caution when connecting the multi-function inputs

to external devices to ensure correct system operation.

Digital Outputs

Multi-Function Output 7 (BI 10) through Multi-Function Output 9 (BI 12) are physical digital outputs on the bypass. Their

function depends on how the bypass is programmed.

Loop Gain

PI Proportional Gain (AO 4) and PI Integral Time (AO 5) are the gain and integral time parameters used by the P1000. The

P1000 PI loop is structured differently than the Metasys loop.

G.4 Bypass Operations by N2

YASKAWA SIEP YAIP1B 01A YASKAWA AC Drive – P1000 Bypass Technical Manual

361

G

Metasys N2 Network Protocol