Yaskawa AC Drive P1000 Bypass Technical Manual User Manual
Page 327
Register No.
Contents
8400H
BYP Command
Bypass Command. Logically OR’d with the physical inputs
Run
Run Rev
Not Used
Transfer to Bypass
Smoke Purge Bypass
Smoke Purge Drive
Motor OR Select
Motor AND Select
X
X
X
X
X
X
X
X
XXXXXXXX
X
X
X
X
X
X
X
X
XXXXXXXX
Not Used
HAND Select
AUTO Select
DRIVE Select
BYPASS Select
Fault Reset
External Fault (EFB)
Not Used
8401H
BYP Freq Ref
Bypass Frequency Reference. This value is sent to the drive if selected by Bypass parameter Z1-07.
The units are determined by drive parameter o1-03.
8402H
BYP DI-oo Command
Bypass Digital Input Command. These bits are logically OR’d with the physical inputs
DI-1 (0/1 for Off/On)
DI-2
DI-3
DI-4
DI-5
DI-6
DI-7
DI-8
X
X
X
X
X
X
X
X
XXXXXXXX
XXXXXXXX
Not Used
XXXXXXXX
8403H
BYP DO-oo Command
Bypass Digital Output Command. These bits allow the digital outputs to be set over a network if
the corresponding digital output function is unused.
Not Used (0/1 for Off/On)
Not Used
Not Used
Not Used
Not Used
Not Used
DO-7
DO-8
X
X
X
X
X
X
X
X
XXXXXXXX
X
X
XXXXXXXX
DO-9
DO-10
Not Used
X
XXXXXX
8404H
Time Set HHMM
Time Set Hours and Minutes. Format is HHMM where HH is hours from 00 to 23 and MM is
minutes from 00 to 59. When new HHMM is set to RTC, the seconds will be set to a value of 0.
8405H
Date Set Year
Date Set Year. Format is YYYY where YYYY is the four digit year from 2000 to 2099.
8406H
Date Set MMDD
Date Set Month and Day. Format is MMDD where MM is month from 01 to 12 and DD is day
from 01 to 31.
8407H
Set RTC
The date and time values in registers 8404H to 8406H are written to the real time clock (RTC) in
the HOA operator connected to the bypass.
0: Do not write values to RTC
1: Write values to RTC
8408H to 843FH
Reserved
D.9 MEMOBUS/Modbus Data Table
YASKAWA SIEP YAIP1B 01A YASKAWA AC Drive – P1000 Bypass Technical Manual
327
D
MEMOBUS/Modbus Communications