U5: pid monitors, For a complete list of u5 – Yaskawa AC Drive P1000 Bypass Technical Manual User Manual

Page 266

background image

No.

(Addr.

Hex)

Name

Description

Analog Output

Level

Unit

U4-22

(7DE)

MEMOBUS/Modbus

Communications

Reference

Displays the drive control data set by MEMOBUS/Modbus

communications register no. 0001H as a four-digit hexadecimal number. No signal output

available

U4-23

(7DF)

Communication Option

Card Reference

Displays drive control data set by an option card as a four-digit hexadecimal

number.

No signal output

available

<1> When reading the value of this monitor via MEMOBUS/Modbus, a value of 8192 is equal to 100% of the drive rated output current.

u

U5: PID Monitors

No.

(Addr.

Hex)

Name

Description

Analog Output

Level

Unit

U5-01

(57)

PID Feedback 1

Displays the PID feedback value.

10 V: 100%

0.01%

<1>

U5-02

(63)

PID Input

Displays the amount of PID input (deviation between PID setpoint and

feedback).

10 V: 100%

0.01%

U5-03

(64)

PID Output

Displays PID control output.

10 V: 100%

0.01%

U5-04

(65)

PID Setpoint

Displays the PID setpoint.

10 V: 100%

0.01%

<1>

U5-05

(7D2)

PID Differential Feedback Displays the 2nd PID feedback value if differential feedback is used (H3-

oo = 16).

10 V: 100%

0.01%

U5-06

(7D3)

PID Adjusted Feedback

Displays the difference of both feedback values if differential feedback is

used (U5-01 - U5-05). If differential feedback is not used, then U5-01 and

U5-06 will be the same.

10 V: 100%

0.01%

U5-30

(3000)

Time Hr Min HHMM

Displays the current time (Hours and Minutes).

No signal output

available

1

U5-31

(3001)

Date Year

Displays the current year.

No signal output

available

1

U5-32

(3002)

Date Mo Day MMDD

Displays the current date (Month and Day).

No signal output

available

1

U5-33

(3003)

Date Week 000W

Displays the current date of the week.

0: Sunday

1: Monday

2: Tuesday

3: Wednesday

4: Thursday

5: Friday

6: Saturday

No signal output

available

1

U5-99

(1599)

PID Setpoint Command

Displays the PID Setpoint commanded by the source.

No signal output

available

0.01%

<1>

<1> Unit, range and resolution is determined by b5-20, b5-38, b5-39, and b5-46

B.13 U: Monitors

266