B.6 E: Motor Parameters

u

E1: V/f Pattern for Motor 1

No.

(Addr.

Hex)

Name

Description

Values

Page

E1-01

(300)

Input Voltage Setting

This parameter must be set to the power supply voltage.

WARNING! Electrical Shock Hazard. Drive input voltage (not motor

voltage) must be set in E1-01 for the protective features of the drive to

function properly. Failure to do so may result in equipment damage

and/or death or personal injury.

Default: 460 V

<1>

Min.: 310
Max.: 510

<1>

109

E1-03

(302)

V/f Pattern Selection

0: 50 Hz, Constant torque 1

1: 60 Hz Saturation

2: 50 Hz Saturation

3: 72 Hz, Constant torque 4 (60 Hz base)

4: 50 Hz, Variable torque 1

5: 50 Hz, Variable torque 2

6: 60 Hz, Variable torque 1

7: 60 Hz, Variable torque 2

8: 50 Hz, High starting torque 1

9: 50 Hz, High starting torque 2

A: 60 Hz, High starting torque 3

B: 60 Hz, High starting torque 4

C: 90 Hz (60 Hz base)

D: 120 Hz (60 Hz base)

E: 180 Hz (60 Hz base)

F: Custom V/f E1-05 setting defines the V/f pattern

Default: F

<2>

Range: 0 to 9;

A to F

109

E1-05

(304)

Maximum Voltage

Only applicable when E1-03 is set to F.

Default:

<3>

Min.: 0.0 V
Max.: 510.0 V

<1>

112

<1> Values shown are specific to 480 Vac bypass drives.
<2> Parameter setting value is not reset to the default value when the drive is initialized.
<3> Default setting is dependent on parameter o2-04, Drive Model Selection.

u

E2: Motor Parameters

No.

(Addr.

Hex)

Name

Description

Values

Page

E2-01

(030E)

Motor Rated Current

Sets the motor nameplate full load current in amps. Automatically set during

Auto-Tuning.

Default:

<1>

Min.: 10% of drive

rated current

Max.: 200% of
drive rated current

<2>

113

E2-03

(310)

Motor No-Load Current

Sets the no-load current for the motor. Automatically set during Auto-Tuning. Default:

<1>

Min.: 0 A
Max.: E2-01

<2>

113

<1> Default setting is dependent on parameter o2-04, Drive Model Selection.
<2> The number of decimal places in the parameter value depends on the drive model.

Refer to Defaults by Drive Model on page 275

for details.

B.6 E: Motor Parameters

244