B.15 defaults by drive model – Yaskawa AC Drive P1000 Bypass Technical Manual User Manual

Page 281

background image

No.

Name

Unit

Default Settings

Drive Model

4A0009

4A0011

4A0018

4A0023

Bypass Model

B007

B011

B014

B021

o2-04

Drive Model Selection

Hex.

96

97

9A

E2-11

Motor Rated Power

kW (HP)

3.7

(5)

5.5

(7.5)

7.5

(10)

11

(15)

b3-04

V/f Gain during Speed Search

%

100

100

100

100

b3-06

Output Current 1 during Speed Search

0.5

0.5

0.5

0.5

b3-07

Output Current 2 during Speed Search

(Speed Estimation Type)

b3-26

Start Speed Search Select

b8-03

Energy Saving Control Filter Time Constant

s

0.50

0.50

0.50

0.50

b8-04

Energy Saving Coefficient Value

245.8

189.5

145.38

140.88

C5-17

Motor Inertia

kgm

2

0.0158

0.0255

0.037

0.053

C6-02

Carrier Frequency Selection

7

7

7

7

E2-01

Motor Rated Current

A

7

9.8

13.3

19.9

E2-02

Motor Rated Slip

Hz

2.7

1.5

1.3

1.7

E2-03

Motor No-Load Current

A

2.3

2.6

4

5.6

E2-05

Motor Line-to-Line Resistance

Ω

3.333

1.595

1.152

0.922

E2-06

Motor Leakage Inductance

%

19.3

18.2

15.5

19.6

E2-10

Motor Iron Loss for Torque Compensation

W

130

193

263

385

L2-02

Momentary Power Loss Ride-Thru Time

s

0.5

0.5

0.8

1

L2-03

Momentary Power Loss Min. Baseblock Time

s

0.6

0.7

0.8

0.9

L2-04

Momentary Power Loss Voltage Recovery Time

s

0.3

0.3

0.3

0.3

L3-24

Motor Acceleration Time for Inertia Calculations

s

0.154

0.168

0.175

0.265

L8-02

Overheat Alarm Level

°C

110

110

110

115

L8-35

Installation Method Selection

2

2

2

2

L8-38

Carrier Frequency Reduction Selection

2

2

2

2

n1-03

Hunting Prevention Time Constant

ms

10

10

10

10

B.15 Defaults by Drive Model

YASKAWA SIEP YAIP1B 01A YASKAWA AC Drive – P1000 Bypass Technical Manual

281

B

Parameter List