V/f pattern settings e1-05, 5 e: motor parameters, Setting a custom v/f pattern (setting f: default) – Yaskawa AC Drive P1000 Bypass Technical Manual User Manual
Page 112

Predefined V/f Patterns for Models D273 to D396 and B124 to B590
The voltage values in the graphs for settings 0 to E apply to applications with 200 V motors. Double the voltage values for
400 V motors. The voltage values in settings 0 to E do not apply to 208, 230, or 460 V motor applications.
Table 5.18 Rated Torque Characteristics, Settings 0 to 3
Setting = 0
50 Hz
Setting = 1
60 Hz
Setting = 2
60 Hz
Setting = 3
72 Hz
0
6
200
1.3 2.5
50
12
V
oltage (V)
Frequency (Hz)
0
6
200
1.5 3
60
12
V
oltage (V)
Frequency (Hz)
0
6
12
200
1.5 3
60
50
V
oltage (V)
Frequency (Hz)
0
6
12
200
1.5 3
72
60
V
oltage (V)
Frequency (Hz)
Table 5.19 Variable Torque Characteristics, Settings 4 to 7
Setting = 4
50 Hz
Setting = 5
50 Hz
Setting = 6
60 Hz
Setting = 7
60 Hz
0
5
200
1.3
25
50
35
V
oltage (V)
Frequency (Hz)
0
6
200
1.3
25
50
50
V
oltage (V)
Frequency (Hz)
0
5
200
1.5
30
60
35
V
oltage (V)
Frequency (Hz)
0
6
200
1.5
30
60
50
V
oltage (V)
Frequency (Hz)
Table 5.20 High Starting Torque, Settings 8 to B
Setting = 8
50 Hz
Setting = 9
50 Hz
Setting = A
60 Hz
Setting = B
60 Hz
0
7
200
1.3 2.5
50
15
V
oltage (V)
Frequency (Hz)
0
9
200
1.3 2.5
50
20
V
oltage (V)
Frequency (Hz)
0
7
200
1.5 3
60
15
V
oltage (V)
Frequency (Hz)
0
11
200
1.5 3
60
20
V
oltage (V)
Frequency (Hz)
Table 5.21 Constant Output, Settings C to F
Setting = C
90 Hz
Setting = D
120 Hz
Setting = E
180 Hz
Setting = F
60 Hz
0
6
12
200
1.5 3
90
60
V
oltage (V)
Frequency (Hz)
0
6
12
200
1.5 3
120
60
V
oltage (V)
Frequency (Hz)
0
6
12
200
1.5 3
180
60
V
oltage (V)
Frequency (Hz)
0
6.9
230
1.5 3
60
13.8
V
oltage (V)
Frequency (Hz)
Setting a Custom V/f Pattern (Setting F: Default)
Setting parameter E1-03 to F allows the user to set up a custom V/f pattern by changing parameter E1-05.
n
V/f Pattern Settings E1-05
If E1-03 is set to a preset V/f pattern (i.e., a value other than F), the user can monitor the maximum voltage in parameters
E1-05. To create a new V/f pattern, set E1-03 to F.
No.
Parameter Name
Setting Range
Default
E1-05
Maximum Voltage
0.0 to 510.0 V
<1>
<2>
<1> Values shown are specific to 480 Vac.
<2> Default setting is determined by parameter E1-03, V/f Pattern Selection.
5.5 E: Motor Parameters
112
YASKAWA SIEP YAIP1B 01A YASKAWA AC Drive – P1000 Bypass Technical Manual