B.15 defaults by drive model – Yaskawa AC Drive P1000 Bypass Technical Manual User Manual

Page 282

background image

No.

Name

Unit

Default Settings

Drive Model

4A0031

4A0038

4A0044

4A0058

Bypass Model

B027

B034

B040

B052

o2-04

Drive Model Selection

Hex.

9C

9D

9E

9F

E2-11

Motor Rated Power

kW (HP)

15

(20)

18.5

(25)

22

(30)

30

(40)

b3-04

V/f Gain during Speed Search

%

100

100

100

100

b3-06

Output Current 1 during Speed Search

0.5

0.5

0.5

0.5

b3-07

Output Current 2 during Speed Search

(Speed Estimation Type)

b3-26

Start Speed Search Select

b8-03

Energy Saving Control Filter Time Constant

s

0.50

0.50

0.50

0.50

b8-04

Energy Saving Coefficient Value

126.26

115.74

103.58

92.54

C5-17

Motor Inertia

kgm

2

0.076

0.138

0.165

0.220

C6-02

Carrier Frequency Selection

7

7

7

7

E2-01

Motor Rated Current

A

26.5

32.9

38.6

52.3

E2-02

Motor Rated Slip

Hz

1.6

1.67

1.7

1.8

E2-03

Motor No-Load Current

A

7.6

7.8

9.2

10.9

E2-05

Motor Line-to-Line Resistance

Ω

0.55

0.403

0.316

0.269

E2-06

Motor Leakage Inductance

%

17.2

20.1

23.5

20.7

E2-10

Motor Iron Loss for Torque Compensation

W

440

508

586

750

L2-02

Momentary Power Loss Ride-Thru Time

s

2

2

2

2

L2-03

Momentary Power Loss Minimum Baseblock Time

s

1

1

1

1.1

L2-04

Momentary Power Loss Voltage Recovery Time

s

0.6

0.6

0.6

0.6

L3-24

Motor Acceleration Time for Inertia Calculations

s

0.244

0.317

0.355

0.323

L8-02

Overheat Alarm Level

°C

120

120

115

120

L8-35

Installation Method Selection

2

2

2

0

L8-38

Carrier Frequency Reduction Selection

2

2

2

2

n1-03

Hunting Prevention Time Constant

ms

10

10

10

10

B.15 Defaults by Drive Model