5.13 Z: Bypass Parameters
Z parameters control bypass-specific functions.
u
Z1: Bypass Control System
n
Z1-01: Initialize
Sets parameters to default values.
No.
Name
Setting Range
Default
Z1-01
Initialize
0 to 3; 8008 to 8011
0
Setting 0: No Initialize
Setting 1: Set all parameters to default values
Setting 2: Set only Bypass Controller parameters to default values
Setting 3: Set only Drive Controller parameters to default values
Setting 8008: Pump
Application Preset for pump applications.
Refer to Application Selection on page 75
for a list of parameters and default values
for this Application Preset.
Setting 8009: Pump w/ PI
Application Preset for pump applications.
Refer to Application Selection on page 75
for a list of parameters and default values
for this Application Preset.
Setting 8010: Fan
Application Preset for pump applications.
Refer to Application Selection on page 75
for a list of parameters and default values
for this Application Preset.
Setting 8011: Fan w/ PI
Application Preset for pump applications.
Refer to Application Selection on page 75
for a list of parameters and default values
for this Application Preset.
n
Z1-02: Password
Allows and restricts access to all parameters. Setting this value equal to the value in Z1-03 toggles access to all parameter
settings, except Z1-02. If the value entered to Z1-02 matches the value entered to Z1-03, the access to all parameters is denied
or granted.
No.
Name
Setting Range
Default
Z1-02
Password
–
–
n
Z1-03: Password Change
The value entered to this parameter is the password.
No.
Name
Setting Range
Default
Z1-03
Password Change
0 to 9999
0
n
Z1-05: Auto Transfer to Bypass Upon Drive Fault
Switches operation to Bypass mode when the drive is running and a drive fault occurs. When the fault is cleared, operation
will switch back to Drive mode
No.
Name
Setting Range
Default
Z1-05
Auto Transfer to Bypass Upon Drive Fault
0, 1
0
Setting 0: Disable
Setting 1: Enable