Z2: bypass control input/output – Yaskawa AC Drive P1000 Bypass Technical Manual User Manual
Page 270
No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
Z1-40
(85ED) Auto Transfer Wait
Time
Auto Xfer Wait T
If Auto Transfer is enabled and a drive fault is detected, the
bypass controller will wait this length of time before switching
to bypass.
Default: 0.0 s
Min.: 0.0
Max.: 300.0
<1> Values are given in Hz, but actual values are dependent upon unit settings using drive parameters o1-03, o1-09, o1-10, and o1-11.
u
Z2: Bypass Control Input/Output
No.
(Addr.
Hex)
Name
Description
Values
Page
Z2-01
(8563)
Digital Input 1 Function
Select
0: Unused (Available for Serial Comms)
3: DRV Multi-Function Input S3 (H1-03 Setting)
4: DRV Multi-Function Input S4 (H1-04 Setting)
5: DRV Multi-Function Input S5 (H1-05 Setting)
6: DRV Multi-Function Input S6 (H1-06 Setting)
7: DRV Multi-Function Input S7 (H1-07 Setting)
21: Run (AUTO Mode)
22: Run Enable (Safety)
23: Run Interlock (BAS)
24: Remote Transfer to Bypass
25: Smoke Purge Bypass Run to Destruction
26: Smoke Purge Drive Run to Destruction at Smoke Purge Preset Speed (See
Z1-10). Bypass controller will stay in this state even if the drive faults or is
unavailable.
27: Motor OR Select (2-Motor OR function; 0/1 for Motor 1/2. Behavior
defined by Z1-11)
28: Motor AND Select (2-Motor AND function; 0/1 for 1/2 motor. If 1 motor,
then look to Motor OR input for selected motor. Behavior defined by Z1-11)
29: Motor 1 Overload Contact. When input is open, declare an OL Fault, issue
an EF0 fault to the drive, delay per EF0 Fault Delay Time (Z1-30), and open
Drive Output (K2) and Bypass (K3) contactors.
30: Motor 2 Overload Contact. When input is open, declare an OL Fault, issue
an EF0 fault to the drive, delay per EF0 Fault Delay Time (Z130), and open
Drive Output (K2) and Bypass (K3) contactors.
31: HAND Select
32: AUTO Select
33: DRIVE/BYPASS Select (0/1 for Drive/Bypass)
34: Fault Reset
35: External Fault (EF0)
36: External Fault (EFB)
37: Run Reverse
Default: 21
Range: 0 to 36
Z2-02
(8564)
Digital Input 2 Function
Select
Default: 22
Range: 0 to 36
Z2-03
(8565)
Digital Input 3 Function
Select
Default: 23
Range: 0 to 36
Z2-04
(8566)
Digital Input 4 Function
Select
Default: 24
Range: 0 to 36
Z2-05
(8567)
Digital Input 5 Function
Select
Default: 25
Range: 0 to 36
Z2-06
(8568)
Digital Input 6 Function
Select
Default: 0
Range: 0 to 36
Z2-07
(8569)
Digital Input 7 Function
Select
Default: 0
Range: 0 to 36
Z2-08
(856A)
Digital Input 8 Function
Select
Default: 29
Range: 0 to 36
Z2-09
(856B)
Digital Input 1 Invert Select
0: Normal. Lack of input signal = OFF
1: Invert. Lack of input signal = ON
Default: 0
Range: 0, 1
Z2-10
(856C)
Digital Input 2 Invert Select
0: Normal. Lack of input signal = OFF
1: Invert. Lack of input signal = ON
Default: 1
Range: 0, 1
Z2-11
(856D)
Digital Input 3 Invert Select
0: Normal. Lack of input signal = OFF
1: Invert. Lack of input signal = ON
Default: 0
Range: 0, 1
Z2-12
(856E)
Digital Input 4 Invert Select
0: Normal. Lack of input signal = OFF
1: Invert. Lack of input signal = ON
Default: 0
Range: 0, 1
Z2-13
(856F)
Digital Input 5 Invert Select
0: Normal. Lack of input signal = OFF
1: Invert. Lack of input signal = ON
Default: 0
Range: 0, 1
B.14 Z: Bypass Parameters
270
YASKAWA SIEP YAIP1B 01A YASKAWA AC Drive – P1000 Bypass Technical Manual