Yaskawa AC Drive P1000 Bypass Technical Manual User Manual
Page 163

Setting 30: Motor 2 Overload Contact
When input is open, declare an oL Fault, issue an EF0 fault to the drive, delay per EF0 Fault Delay Time (Z1-30), and open
Bypass (K3) contactors.
Setting 31: HAND Select
When this is selected, the HAND function command will come from a digital input while the HAND key on the HOA operator
will be ignored. If both HAND and AUTO functions are configured to come from digital inputs, the lack of both of these
inputs being active will put the HOA function into the OFF state. The OFF key on the HOA operator will always place the
HOA function to the OFF state.
Setting 32: AUTO Select
When this is selected, the AUTO function command will come from a digital input while the AUTO key on the HOA operator
will be ignored. If both HAND and AUTO functions are configured to come from digital inputs, the lack of both of these
inputs being active will put the HOA function into the OFF state. The OFF key on the HOA operator will always place the
HOA function to the OFF state
Setting 33: DRIVE/BYPASS Select
When this is selected, the DRIVE/BYPASS select function command will come from a digital input while the DRV/BYP key
on the HOA operator will be ignored.
Input OFF: Drive Mode is selected.
Input ON: Bypass Mode is selected.
Setting 34: Fault Reset
Setting 35: External Fault (EF0)
Setting 36: External Fault (EFB)
Setting 37: Run Reverse (AUTO Mode)
n
Z2-09 to Z2-16: Digital Input 1 to 8 Invert Select
No.
Name
Setting Range
Default
Z2-09
Digital Input 1 Invert Select
0, 1
0
Z2-10
Digital Input 2 Invert Select
0, 1
1
Z2-11
Digital Input 3 Invert Select
0, 1
0
Z2-12
Digital Input 4 Invert Select
0, 1
0
Z2-13
Digital Input 5 Invert Select
0, 1
0
Z2-14
Digital Input 6 Invert Select
0, 1
0
Z2-15
Digital Input 7 Invert Select
0, 1
0
Z2-16
Digital Input 8 Invert Select
0, 1
1
n
Bypass Digital Input Invert Settings
Table 5.30 Bypass Digital Input Invert Settings
Setting
Function
Page
0
Normal
Setting
Function
Page
1
Invert
Setting 0: Normal
Lack of input signal = OFF
Setting 1: Invert
Lack of input signal = ON
n
Z2-23 to Z2-26: Digital Output 7 to 10 Function Select
No.
Name
Setting Range
Default
Z2-23
Digital Output 7 Function Select
0 to 22; 99
7
Z2-24
Digital Output 8 Function Select
0 to 22; 99
10
Z2-25
Digital Output 9 Function Select
0 to 22; 99
12
Z2-26
Digital Output 10 Function Select
0 to 22; 99
15
5.13 Z: Bypass Parameters
YASKAWA SIEP YAIP1B 01A YASKAWA AC Drive – P1000 Bypass Technical Manual
163
5
Programming