B.15 Defaults by Drive Model
The following tables show parameters and default settings that change with the drive model selection (o2-04).
Table B.4 208 Vac Bypass Drive Default Settings by Drive Model Selection
No.
Name
Unit
Default Settings
–
Drive Model
–
2A0004
2A0006
2A0008
Bypass Model
–
D002
D003
D004
D007
o2-04
Drive Model Selection
Hex.
62
63
64
E2-11
Motor Rated Output
kW (HP)
0.75
(0.75)
1.1
(1)
1.5
(2)
b3-04
V/f Gain during Speed Search
%
100
100
100
b3-06
Output Current 1 during Speed Search
–
1
0.5
0.5
b3-07
Output Current 2 during Speed Search
(Speed Estimation Type)
–
–
–
–
b3-26
Start Speed Search Select
–
–
–
–
b8-03
Energy Saving Control Filter Time Constant
s
0.50
0.50
0.50
b8-04
Energy Saving Coefficient Value
–
223.7
196.6
169.4
C5-17
Motor Inertia
kgm
2
0.0028
0.0068
0.0068
C6-02
Carrier Frequency Selection
–
7
7
7
E2-01
Motor Rated Current
A
3.3
4.9
6.2
E2-02
Motor Rated Slip
Hz
2.5
2.6
2.6
E2-03
Motor No-Load Current
A
1.8
2.3
2.8
E2-05
Motor Line-to-Line Resistance
Ω
5.156
3.577
1.997
E2-06
Motor Leakage Inductance
%
13.8
18.5
18.5
E2-10
Motor Iron Loss for Torque Compensation
W
26
38
53
L2-02
Momentary Power Loss Ride-Thru Time
s
0.1
0.2
0.3
L2-03
Momentary Power Loss Minimum Baseblock Time
s
0.3
0.4
0.4
L2-04
Momentary Power Loss Voltage Recovery Time
s
0.3
0.3
0.3
L3-24
Motor Acceleration Time for Inertia Calculations
s
0.142
0.142
0.166
L8-02
Overheat Alarm Level
°C
115
115
115
L8-35
Installation Method Selection
–
2
2
2
L8-38
Carrier Frequency Reduction Selection
–
2
2
2
n1-03
Hunting Prevention Time Constant
ms
10
10
10
B.15 Defaults by Drive Model
YASKAWA SIEP YAIP1B 01A YASKAWA AC Drive – P1000 Bypass Technical Manual
275
B
Parameter List