Starting Auto-Tuning
WARNING! Sudden Movement Hazard. The drive and motor may start unexpectedly during Auto-Tuning, which could result in death or
serious injury. Ensure the area surrounding the drive motor and load are clear before proceeding with Auto-Tuning.
WARNING! Electrical Shock Hazard. High voltage will be supplied to the motor when Stationary Auto-Tuning is performed even with the
motor stopped, which could result in death or serious injury. Do not touch the motor until Auto-Tuning has been completed.
NOTICE: Rotational Auto-Tuning will not function properly if the motor cannot spin freely. Failure to comply could result in improper operation
of the drive. Ensure the motor can freely spin before beginning Auto-Tuning.
Enter the required information from the motor nameplate. Press
to proceed to the Auto-Tuning start display.
Note:
These instructions continue from Step 6 in “Enter Data from the Motor Nameplate”.
Step
Display/Result
1. After entering the data listed on the motor nameplate, press
to confirm.
DRV-OFF
0.00 Hz/ 0.00A
Tuning Ready?
Auto-Tuning
DATA
ESC
Press HAND Key
2. Press
HAND
to activate Auto-Tuning.
flashes. The drive begins by injecting current
into the motor for about 1 min, and then starts to rotate the motor.
DRV-OFF
0.00 Hz/ 0.00A
Tuning Ready?
Tune Proceeding
Press HAND Key
3. Auto-Tuning finishes in approximately one to two minutes.
MODE
Tune Successful
End
RESET
u
T1: Parameter Settings during Induction Motor Auto-Tuning
The T1-oo parameters set the Auto-Tuning input data for induction motor tuning.
Note:
For motors operating in the field weakening range, first perform the Auto-Tuning with the base data. After Auto-Tuning is complete, change
E1-04, Maximum Output Frequency, to the desired value.
n
T1-01: Auto-Tuning Mode Selection
Sets the type of Auto-Tuning to be used. Refer to the User Manual packaged with the drive for details on the different types
of Auto-Tuning.
No.
Name
Setting Range
Default
T1-01
Auto-Tuning Mode Selection
2, 3 (V/f)
2 (V/f)
Setting 2: Stationary Auto-Tuning for Line-to-Line Resistance
Setting 3: Rotational Auto-Tuning for V/f Control Energy Saving
n
T1-02: Motor Rated Power
Sets the motor rated power according to the motor nameplate value.
Note:
Use the following formula to convert HP to kW: kW = HP x 0.746.
No.
Name
Setting Range
Default
T1-02
Motor Rated Power
0.00 to 650.00 kW
Determined by o2-04
n
T1-03: Motor Rated Voltage
Sets the motor rated voltage according to the motor nameplate value. Enter the voltage base speed when the motor operates
above base speed. Enter the voltage needed to operate the motor under no-load conditions at rated speed to T1-03.
No.
Name
Setting Range
Default
T1-03
Motor Rated Voltage
0.0 to 255.0 V
<1>
200.0 V
<1>
<1> Values shown are specific to 200 V Class. Double the value for 400 V Class.