Yaskawa AC Drive P1000 Bypass Technical Manual User Manual
Page 273

No.
(Addr.
Hex)
Name
Description
Values
Page
Z4-08
(8707)
Subnet Mask 4
Sets the fourth most significant octet of network static subnet mask.
Default: 0
Range: 0 to 255
Z4-09
(8708)
Gateway IP Address 1
Sets the most significant octet of network gateway address.
Default: 192
Range: 0 to 255
Z4-10
(87098)
Gateway IP Address 2
Sets the second most significant octet of network gateway address.
Default: 168
Range: 0 to 255
Z4-11
(870A)
Gateway IP Address 3
Sets the third most significant octet of network gateway address.
Default: 1
Range: 0 to 255
Z4-12
(870B)
Gateway IP Address 4
Sets the fourth most significant octet of network gateway address.
Default: 1
Range: 0 to 255
Z4-13
(870C)
IP Address Mode Select
0: User-Defined (Static IP)
1: BOOTP
2: DHCP
Default: 2
Range: 0 to 2
Z4-14
(870D)
Duplex Select
0: Forced Half Duplex
1: Auto Negotiate Duplex Mode and Communication Speed
2: Forced Full Duplex
Default: 1
Range: 0 to 2
Z4-15
(870E)
Speed Mode Setting
10: 10 Mbps
100: 100 Mbps
Default: 10
Range: 10, 100
Z4-16
(870F)
Communication Loss
Timeout
Control connection timeout value for detection of communication loss.
Default: 0 s
Min.: 0
Max.: 300
Z4-17
(8710)
Ethernet Speed Scale
AC/DC Drive Object, Instance 1, Attribute 22
Default: 0
Min.: -15
Max.: 15
Z4-18
(8711)
Ethernet Current Scale
AC/DC Drive Object, Instance 1, Attribute 23
Default: 0
Min.: -15
Max.: 15
Z4-19
(8712)
Ethernet Torque Scale
AC/DC Drive Object, Instance 1, Attribute 24
Default: 0
Min.: -15
Max.: 15
Z4-20
(8713)
Ethernet Power Scale
AC/DC Drive Object, Instance 1, Attribute 26
Default: 0
Min.: -15
Max.: 15
Z4-21
(8714)
Ethernet Voltage Scale
AC/DC Drive Object, Instance 1, Attribute 27
Default: 0
Min.: -15
Max.: 15
Z4-22
(8715)
Ethernet Time Scale
AC/DC Drive Object, Instance 1, Attribute 28
Default: 0
Min.: -15
Max.: 15
Z4-23 to
Z4-32
(8716 to
871F)
Dynamic Output Assembly
Parameters DOA116 1 to
DOA116 10
Parameters used in Output Assembly 116
Default: 0
Range: 0 to FFFF
B.14 Z: Bypass Parameters
YASKAWA SIEP YAIP1B 01A YASKAWA AC Drive – P1000 Bypass Technical Manual
273
B
Parameter List