L6: Torque Detection

No.

(Addr.

Hex)

Name

Description

Values

Page

L6-02

(4A2)

Torque Detection Level 1

Sets the overtorque and undertorque detection level.

Default: 15%

Min.: 0

Max.: 300

135

L6-03

(4A3)

Torque Detection Time 1

Sets the time an overtorque or undertorque condition must exist to trigger

torque detection 1.

Default: 10.0 s

Min.: 0.0

Max.: 10.0

135

L6-13

(62E)

Motor Underload Protection

Selection

Sets the motor underload protection (ULo) based on motor load.

0: Overtorque/undertorque detection enabled

1: Base frequency motor load enabled

Default: 0

Range: 0, 1

136

L6-14

(62F)

Motor Underload Protection

Level at Minimum

Frequency

Sets the UL6 detection level at minimum frequency by percentage of drive

rated current.

Default: 15%

Min.: 0

Max.: 300

136

u

L8: Drive Protection

No.

(Addr.

Hex)

Name

Description

Values

Page

L8-02

(4AE)

Overheat Alarm Level

An overheat alarm occurs when heatsink temperature exceeds the L8-02 level. Default:

<1>

Min.: 50 °C

Max.: 150 °C

136

L8-05

(4B1)

Input Phase Loss Protection

Selection

Selects the detection of input current phase loss, power supply voltage

imbalance, or main circuit electrolytic capacitor deterioration.

0: Disabled

1: Enabled

Default: 1

Range: 0, 1

136

L8-06

(4B2)

Input Phase Detection Level

When ripple is observed in the DC bus, expansion of the input bias is

calculated. This value becomes the input phase if the difference between the

maximum and minimum values of the ripple is greater than the value set to

L8-06.

Detection Level = 100% = Voltage class x √2

Default:

<1>

Min.: 0.0%

Max.: 50.0%

136

L8-07

(4B3)

Output Phase Loss

Protection Selection

0: Disabled

1: Enabled (triggered by a single phase loss)

2: Enabled (triggered when two phases are lost)

Default: 1

Range: 0 to 2

137

L8-09

(4B5)

Output Ground Fault

Detection Selection

0: Disabled

1: Enabled

Default:

<1>

Range: 0, 1

137

L8-38

(4EF)

Carrier Frequency

Reduction

0: Disabled

1: Enabled below 6 Hz

2: Enabled for the entire speed range

Default:

<1>

Range: 0 to 2

138

<1> Default setting is dependent on parameter o2-04, Drive Model Selection.

B.9 L: Protection Function

252