5.5 E: Motor Parameters
E parameters cover V/f pattern and motor data settings.
u
E1: V/f Pattern for Motor 1
n
E1-01: Input Voltage Setting
Adjusts the levels of some protective features of the drive (overvoltage, Stall Prevention, etc.). Set this parameter to the nominal
voltage of the AC power supply.
NOTICE: Set parameter E1-01 to match the input voltage of the drive. Drive input voltage (not motor voltage) must be set in E1-01 for the
protective features to function properly. Failure to set the correct drive input voltage will result in improper drive operation.
No.
Parameter Name
Setting Range
Default
E1-01
Input Voltage Setting
310 to 510 V
460 V
<1>
<1> Values shown are specific to 480 Vac bypass drives.
E1-01 Related Values
The input voltage setting determines the overvoltage and undervoltage detection levels, the KEB function, and the overvoltage
suppression function.
Voltage
Setting Value of E1-01
(Approximate Values)
Uv Detection Level (L2-05)
208 Vac Bypass Drives
All settings
190 V
480 Vac Bypass Drives
Setting > 460 V
440 V
n
V/f Pattern Settings (E1-03)
The drive uses a V/f pattern to adjust the output voltage relative to the frequency reference. There are 15 different predefined
V/f patterns (setting 0 to E) from which to select, each with varying voltage profiles, saturation levels (frequency at which
maximum voltage is reached), and maximum frequencies. Additionally, one custom V/f pattern is available (setting F) that
requires the user to create the pattern using parameters E1-04 through E1-10.
n
E1-03: V/f Pattern Selection
Selects the V/f pattern for the drive and motor from 15 predefined patterns or creates a custom V/f pattern.
No.
Parameter Name
Setting Range
Default
E1-03
V/f Pattern Selection
0 to 9; A to FF
F
Setting a Predefined V/f Pattern (Setting 0 to F)
Choose the V/f pattern that best meets the application demands from the table below. Set the correct value to E1-03. Parameter
E1-05 can only be monitored, not changed.
Note:
1. Setting an improper V/f pattern may result in low motor torque or increased current due to overexcitation.
2. Drive initialization does not reset parameter E1-03.
Table 5.9 Predefined V/f Patterns
Setting
Specification
Characteristic
Application
0
50 Hz
Constant torque
For general purpose applications. Torque remains constant
regardless of changes to speed.
1
60 Hz Saturation
2
50 Hz Saturation
3
72 Hz (with 60 Hz base)
4
50 Hz, Variable torque 1
Variable torque
For fans, pumps, and other applications where the required
torque changes as a function of the speed.
5
50 Hz, Variable torque 2
6
60 Hz, Variable torque 1
7
60 Hz, Variable torque 2