Binary input objects – Yaskawa AC Drive P1000 Bypass Technical Manual User Manual
Page 297

Object ID
Object Name
Modbus
Address
Precision
Range
Units
PV Access
AV13
Output Power
0047H
XXXX.X
(for drives rated
above 11 kVA)
XXX.XX
(for drives rated
11 kVA or
lower)
–
kW
R
AV14
Torque Reference
0048H
XXXX.X
–
%
R
AV15
MF Input Status
002BH
–
–
–
R
AV16
Drive Status 2
002CH
–
–
–
R
AV17
MF Output Status
002DH
–
–
–
R
AV18
DC Bus Voltage
0031H
XXXXX
–
Volts
R
AV19
PI Feedback Level
0038H
XXXX.X
–
%
R
AV20
PI Input Level
0039H
XXXX.X
–
%
R
AV21
PI Output Level
003AH
XXXX.X
–
%
R
AV22
Drive SW Num
004DH
XXXXX
–
–
R
AV23
Bypass SW Num
8791H
XXXXX
–
–
R
AV24
Comm Error Detail
003DH
–
–
–
R
AV25
KVA Setting
003EH
XXXXX
–
–
R
AV26
Control Method
0043H
XXXXX
–
–
R
AV27
Accel Time
0200H
XXXX.X
0.0 to 6000.0
Sec
W
AV28
Decel Time
0201H
XXXX.X
0.0 to 6000.0
Sec
W
AV29
<1>
Parameter Number
–
XXXXX
0 to FFFFH
–
W
AV30
<1>
Parameter Data
–
XXXXX
0 to FFFFH
–
W
AV31
Motor Current
8780H
XXXX.X
–
Amps
R
AV32
120 V to Kx Coils
8790H
XXXXX
–
Volts
R
<1>
Refer to Accessing Bypass Parameters and the Enter Command on page 301
for an explanation of how to read and write drive parameters not
listed in the analog or binary objects.
u
Binary Input Objects
Table C.7 Binary Input Objects
Object ID
Object Name
Modbus
Address
Active Text
Inactive Text
PV Access
BI1
Input Terminal 1
002BH:bit 0
ON
OFF
R
BI2
Input Terminal 2
002BH:bit 1
ON
OFF
R
BI3
Input Terminal 3
002BH:bit 2
ON
OFF
R
BI4
Input Terminal 4
002BH:bit 3
ON
OFF
R
BI5
Input Terminal 5
002BH:bit 4
ON
OFF
R
BI6
Input Terminal 6
002BH:bit 5
ON
OFF
R
BI7
Input Terminal 7
002BH:bit 6
ON
OFF
R
BI8
Multi-Function Out 1
0020H:bit 5
ON
OFF
R
BI9
Multi-Function Out 2
0020H:bit 6
ON
OFF
R
BI10
BYP DI-1 STAT
8781H: bit 0
ON
OFF
R
BI11
BYP DI-2 STAT
8781H: bit 1
ON
OFF
R
BI12
BYP DI-3 STAT
8781H: bit 2
ON
OFF
R
BI13
BYP DI-4 STAT
8781H: bit 3
ON
OFF
R
BI14
BYP DI-5 STAT
8781H: bit 4
ON
OFF
R
BI15
BYP DI-6 STAT
8781H: bit 5
ON
OFF
R
BI16
BYP DI-7 STAT
8781H: bit 6
ON
OFF
R
BI17
BYP DI-8 STAT
8781H: bit 7
ON
OFF
R
BI18
BYP DO-1 STAT
8782H: bit 0
ON
OFF
R
C.6 BACnet Objects Supported
YASKAWA SIEP YAIP1B 01A YASKAWA AC Drive – P1000 Bypass Technical Manual
297
C
BACnet Communications