Device object – Yaskawa AC Drive P1000 Bypass Technical Manual User Manual

Page 300

background image

Object ID

Object Name

Modbus

Address

Active Text

Inactive Text

PV Access

BV69

BYP BYPASS Sel CMD

8400H: bit 12

BYP

DRV

C

BV70

BYP Fault Reset CMD

8400H: bit 13

ON

OFF

C

BV71

BYP Ext Fault CMD

8400H: bit 14

ON

OFF

C

BV72

BYP DI-01 Command

8402H: bit 0

ON

OFF

W

BV73

BYP DI-02 Command

8402H: bit 1

ON

OFF

W

BV74

BYP DI-03 Command

8402H: bit 2

ON

OFF

W

BV75

BYP DI-04 Command

8402H: bit 3

ON

OFF

W

BV76

BYP DI-05 Command

8402H: bit 4

ON

OFF

W

BV77

BYP DI-06 Command

8402H: bit 5

ON

OFF

W

BV78

BYP DI-07 Command

8402H: bit 6

ON

OFF

W

BV79

BYP DI-08 Command

8402H: bit 7

ON

OFF

W

BV80

BYP HAND Mode Status

8784H: bit 0

ON

OFF

R

BV81

BYP OFF Mode Status

8784H: bit 1

ON

OFF

R

BV82

BYP AUTO Mode Status

8784H: bit 2

ON

OFF

R

BV83

BYP DRV Mode Status

8784H: bit 3

ON

OFF

R

BV84

BYP BYPASS Mode Stat

8784H: bit 4

ON

OFF

R

BV85

BYP Smk Prg BYP Stat

8784H: bit 5

ACTIVE

OFF

R

BV86

BYP Smk Prg DRV Stat

8784H: bit 6

ACTIVE

OFF

R

BV87

BYP Safety Status

8784H: bit 7

OPEN

CLOSED

R

BV88

BYP BAS Interlk Stat

8785H: bit 0

OPEN

CLOSED

R

BV89

BYP RUN Status

8785H: bit 1

RUN

OFF

R

BV90

BYP Fault Status

8785H: bit 2

FAULT

OFF

R

BV91

BYP Auto Xfer Status

8785H: bit 3

ACTIVE

OFF

R

BV92

BYP Remote Xfer Stat

8785H: bit 4

ACTIVE

OFF

R

BV93

BYP Energy Save Stat

8785H: bit 5

ACTIVE

OFF

R

BV94

BYP Motor 1 Sel Stat

8785H: bit 6

SELECT

OFF

R

BV95

BYP Motor 2 Sel Stat

8785H: bit 7

SELECT

OFF

R

BV96

BYP Drive Flt Status

8786H: bit 0

FAULT

OFF

R

BV97

BYP Safety Flt Stat

8786H: bit 1

FAULT

OFF

R

BV98

BYP BAS ILock Status

8786H: bit 2

FAULT

OFF

R

BV99

BYP Ext Fault Stat

8786H: bit 3

FAULT

OFF

R

BV100

Not Used BV100

8786H: bit 4

FAULT

OFF

R

BV101

BYP Motor OL Stat

8786H: bit 5

FAULT

OFF

R

BV102

BYP Motor 1 OL Stat

8786H: bit 6

FAULT

OFF

R

BV103

BYP Mtr 2 OL Stat

8786H: bit 7

FAULT

OFF

R

BV104

BYP Input Phase Loss

8787H: bit 0

FAULT

OFF

R

BV105

BYP Drive Comms

8787H: bit 2

FAULT

OFF

R

BV106

BYP Loss Of Load

8787H: bit 5

FAULT

OFF

R

BV107

BYP Option Brd Comms

8787H: bit 3

FAULT

OFF

R

<1>

Refer to Accessing Bypass Parameters and the Enter Command on page 301

for an explanation of how to read and write drive parameters not

listed in the analog or binary objects.

u

Device Object

The Device Object fully describes the BACnet device to the network. Notable is that the Device Object Instance ID and the

Device Object Name are configurable.
The Device Object Instance ID is a unique internetwork-wide numerical value. It is a 22-bit value that can range from 0 to

4,194,303. It is configurable by parameters Z3-08 and Z3-09. Any changes to these parameters will not take effect until the

power is cycled to the bypass.
The Device Object Name is a unique internetwork-wide character string. It is a 20-character string. It is writable from the

BACnet network. Any new string written will not take effect until the power is cycled to the bypass.

C.6 BACnet Objects Supported

300