Fault detection, Fault displays, causes, and possible solutions, 4 fault detection – Yaskawa AC Drive P1000 Bypass Technical Manual User Manual
Page 176

6.4 Fault Detection
u
Fault Displays, Causes, and Possible Solutions
Faults are detected for drive protection, and cause the drive to stop while triggering the fault output terminal TB1 10, 11, and
12. Remove the cause of the fault and manually clear the fault before attempting to run the drive again.
Table 6.8 Detailed Fault Displays, Causes, and Possible Solutions
HOA Keypad Display
Fault Name
bAT
HOA Keypad Battery Voltage Low
Cause
Possible Solution
The HOA keypad battery is low
Replace the HOA keypad battery.
HOA Keypad Display
Fault Name
bUS
Option Communication Error
• The connection was lost after establishing initial communication.
• Only detected when the run command frequency reference is assigned to an option card.
Cause
Possible Solution
No signal was received from the PLC
• Check for faulty wiring.
• Correct the wiring.
• Check for disconnected cables and short circuits and repair as needed.
Faulty communications wiring or an existing short
circuit
Communication data error occurred due to noise
• Check the various options available to minimize the effects of noise.
• Counteract noise in the control circuit, main circuit, and ground wiring.
• Ensure that other equipment such as switches or relays do not cause noise. Use surge absorbers if
necessary.
• Use only recommended cables or other shielded line. Ground the shield on the controller side or
the drive input power side.
• Separate all communication wiring from drive power lines.
The option card is damaged
Replace the option card if there are no problems with the wiring and the error continues to occur.
The option card is not properly connected to the
drive
• The connector pins on the option card do not line up properly with the connector pins on the drive.
• Reinstall the option card.
HOA Keypad Display
Fault Name
CE
MEMOBUS/Modbus Communication Error
Control data was not received for the CE detection time set to H5-09.
Cause
Possible Solution
Faulty communications wiring or an existing short
circuit
• Check for faulty wiring.
• Correct the wiring.
• Check for disconnected cables and short circuits and repair as needed.
Communication data error occurred due to noise
• Check the various options available to minimize the effects of noise.
• Counteract noise in the control circuit, main circuit, and ground wiring.
• Use only recommended cables or other shielded line. Ground the shield on the controller side or
the drive input power side.
• Ensure that other equipment such as switches or relays do not cause noise. Use surge suppressors
if required.
• Separate all communication wiring from drive power lines.
HOA Keypad Display
Fault Name
CoF
Current Offset Fault
Cause
Possible Solution
The drive tried to adjust the current offset value
beyond the allowable range. This is due to residual
induction current in the motor (e.g., during sudden
deceleration or when coasting) when the drive
attempted to start the motor.
• Create a motor restart sequence that allows enough time for residual induction voltage to dissipate.
• Enable Speed Search at start (b3-01 = 1).
The current sensor in the drive is damaged
If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa
representative for instructions on replacing the control board.
6.4 Fault Detection
176
YASKAWA SIEP YAIP1B 01A YASKAWA AC Drive – P1000 Bypass Technical Manual