5 e: motor parameters, Table 5.16 high starting torque, settings 8 to b, Table 5.17 constant output, settings c to f – Yaskawa AC Drive P1000 Bypass Technical Manual User Manual
Page 111

Predefined V/f Patterns for Models D030 to D211 and B014 to B096
The voltage values in the graphs for settings 0 to E apply to applications with 200 V motors. Double the voltage values for
400 V motors. The voltage values in settings 0 to E do not apply to 208, 230, or 460 V motor applications.
Table 5.14 Rated Torque Characteristics, Settings 0 to 3
Setting = 0
50 Hz
Setting = 1
60 Hz
Setting = 2
60 Hz
Setting = 3
72 Hz
0
7
200
1.3 2.5
50
14
V
oltage (V)
Frequency (Hz)
0
7
14
200
1.5 3
60
V
oltage (V)
Frequency (Hz)
V
oltage (V)
Frequency (Hz)
0
7
14
200
1.5 3
60
50
0
7
14
200
1.5 3
72
60
V
oltage (V)
Frequency (Hz)
Table 5.15 Variable Torque Characteristics, Settings 4 to 7
Setting = 4
50 Hz
Setting = 5
50 Hz
Setting = 6
60 Hz
Setting = 7
60 Hz
V
oltage (V)
Frequency (Hz)
0
6
200
1.3
25
50
35
0
7
200
1.3
25
50
50
V
oltage (V)
Frequency (Hz)
V
oltage (V)
Frequency (Hz)
0
6
200
1.5
30
60
35
0
7
200
1.5
30
60
50
V
oltage (V)
Frequency (Hz)
Table 5.16 High Starting Torque, Settings 8 to B
Setting = 8
50 Hz
Setting = 9
50 Hz
Setting = A
60 Hz
Setting = B
60 Hz
0
9
200
1.3 2.5
50
18
V
oltage (V)
Frequency (Hz)
V
oltage (V)
Frequency (Hz)
0
11
200
1.3 2.5
50
23
V
oltage (V)
Frequency (Hz)
0
9
200
1.5 3
60
18
0
13
200
1.5 3
60
23
V
oltage (V)
Frequency (Hz)
Table 5.17 Constant Output, Settings C to F
Setting = C
90 Hz
Setting = D
120 Hz
Setting = E
180 Hz
Setting = F
60 Hz
0
7
14
200
1.5 3
90
60
V
oltage (V)
Frequency (Hz)
0
7
14
200
1.5 3
120
60
V
oltage (V)
Frequency (Hz)
0
7
14
200
1.5 3
180
60
V
oltage (V)
Frequency (Hz)
V
oltage (V)
Frequency (Hz)
0
8.1
16.1
230
1.5 3
60
5.5 E: Motor Parameters
YASKAWA SIEP YAIP1B 01A YASKAWA AC Drive – P1000 Bypass Technical Manual
111
5
Programming