Yaskawa AC Drive P1000 Bypass Technical Manual User Manual
Page 102
No.
Name
Setting Range
Default
b5-91
EZ Minimum Speed
0.0 to 400.0 Hz
<1>
or 0 to 24000 RPM
0.0
<1> Unit and resolution are determined by b5-20, b5-39, and b5-46. Internally limited to b5-38. Changing b5-20, b5-38 and b5-39 will not automatically
update the value of this parameter.
n
b5-92: EZ Sleep Level
When the drive output frequency (or speed) is at or below this level for the time set in b5-93, the drive will go to sleep.
The internal lower limit of this parameter is b5-91 (EZ Min Speed) + 1 Hz.
No.
Name
Setting Range
Default
b5-92
EZ Sleep Level
0.0 to 400.0 Hz
<1>
or 0 to 24000 RPM
0.0
<1> Unit and resolution are determined by b5-20, b5-39, and b5-46. Internally limited to b5-38. Changing b5-20, b5-38 and b5-39 will not automatically
update the value of this parameter.
n
b5-93: EZ Sleep Time
The drive will go to sleep when the drive output frequency is at or below the level set to b5-92 for the time set in this parameter.
No.
Name
Setting Range
Default
b5-93
EZ Sleep Tim
0.0 to 10000.0
<1>
5.0 s
<1> Unit and resolution are determined by b5-20, b5-39, and b5-46. Internally limited to b5-38. Changing b5-20, b5-38 and b5-39 will not automatically
update the value of this parameter.
n
b5-94: EZ Wake-up Level
If b5-95 is set to 0 (Absolute), the drive wakes-up when the PID Feedback (H3-oo = 20) drops below this level for the time
set in b5-96. For reverse-acting, the PID Feedback has to be above this level for the time set in b5-96.
If b5-95 is set to 1 (Setpoint Delta), the drive wakes-up when the PID Feedback (H3-oo = 20) drops below the PID Setpoint
minus this level (for normal acting PID) for the time set in b5-96. For reverse-acting, Wake-up level is PID Setpoint plus this
level. The PID Feedback has to be above the wake-up level for the time set in b5-96.
No.
Name
Setting Range
Default
b5-94
EZ Wake-up Level
0.00 to 600.00%
<1>
0.00
<1> Unit and resolution are determined by b5-20, b5-39, and b5-46. Internally limited to b5-38. Changing b5-20, b5-38 and b5-39 will not automatically
update the value of this parameter.
n
b5-95: EZ Wake-up Mode
Sets how the wake-up level is determined.
No.
Name
Setting Range
Default
b5-95
EZ Wake-up Mode
0, 1
<1>
0
<1> Unit and resolution are determined by b5-20, b5-39, and b5-46. Internally limited to b5-38. Changing b5-20, b5-38 and b5-39 will not automatically
update the value of this parameter.
Setting 0: Absolute
Setting 1: Setpoint Data
n
b5-96: EZ Wake-up Time
The drive will wake up when the PID Feedback drops below the b5–94, EZ Wake-up Level for the time set in this parameter.
No.
Name
Setting Range
Default
b5-96
EZ Wake-up Time
0.0 to 1000.0
<1>
1.0 s
<1> Unit and resolution are determined by b5-20, b5-39, and b5-46. Internally limited to b5-38. Changing b5-20, b5-38 and b5-39 will not automatically
update the value of this parameter.
5.2 b: Application
102
YASKAWA SIEP YAIP1B 01A YASKAWA AC Drive – P1000 Bypass Technical Manual