beautypg.com

H3: multi-function analog inputs – Yaskawa AC Drive P1000 Bypass Technical Manual User Manual

Page 117

background image

Setting 14: Fault Reset

When the drive detects a fault condition, the fault output contact closes, the drive output shuts off, and the motor coasts to

stop (specific stopping methods can be selected for some faults such as L1-04 for motor overheat). After removing the Run

command, clear the fault either by pressing the RESET key on the HOA keypad or closing a digital input configured as a Fault

Reset (H1-oo = 14).

Note:

Remove the Run command prior to resetting a fault. Fault Reset commands are ignored while the Run command is present.

Setting 19: PID Disable

Close a digital input to indefinitely disable the PID function. When the input is released, the drive resumes PID operation.

Refer to PID Block Diagram on page 93

.

Setting 24: External Fault

The External fault command stops the drive when problems occur with external devices.
To use the External fault command, set one of the multi-function digital inputs to 24. The HOA keypad will display EFo

where o is the number of the terminal to which the external fault signal is assigned.
For example, if an external fault signal is input to terminal DI-3, “EF3” will be displayed.
The conditions of setting 24 are:
• Terminal status is normally open
• Detection condition is always detected
• Stopping method is coast to stop.

Setting 60: DC Injection Braking Command

DC Injection Braking is activated when a DC Injection Braking command is input while the drive is stopped. DC Injection

Braking is released when a Run command or a Jog command is input.

Refer to b2: DC Injection Braking and Short Circuit

Braking on page 85

for details on setting up the DC Injection Braking function.

The diagram below illustrates DC Injection Braking:

DC Injection braking

command

FWD Run command

Output frequency

DC Injection
braking

DC Injection
braking

DC Injection Braking

Start Frequency

(b2-01)

OFF

OFF

OFF

OFF

ON

ON

Figure 5.22 DC Injection Braking Input Timing Diagram

u

H3: Multi-Function Analog Inputs

The drive is equipped with three multi-function analog input terminals: A1, A2, and A3.

Refer to Multi-Function Analog

Input Terminal Settings on page 120

for a listing of the functions that can be set to these terminals.

n

H3-01: Terminal A1 Signal Level Selection

Selects the input signal level for analog input A1. Set jumper S1 on the terminal board accordingly for voltage input or current

input.

No.

Name

Setting Range

Default

H3-01

Terminal A1 Signal Level Selection

0 to 3

0

Setting 0: 0 to 10 V with Zero Limit

The input level is 0 to 10 Vdc with zero limit. The minimum input level is limited to 0%, so that a negative input signal due

to gain and bias settings will be read as 0%.

Setting 1: 0 to 10 V without Zero Limit

The input level is 0 to 10 Vdc without zero limit. If the resulting voltage is negative after being adjusted by gain and bias

settings, then the motor will rotate in reverse.

5.7 H: Terminal Functions

YASKAWA SIEP YAIP1B 01A YASKAWA AC Drive – P1000 Bypass Technical Manual

117

5

Programming