Bypass enclosures, Bypass product options – Yaskawa AC Drive P1000 Bypass Technical Manual User Manual
Page 31

Bypass Model
HP
Input (A)
Output (A)
Drive Model
P1B1
Models
without
Power
Options
P1B1
Models
with
PY Option
P1B2 and
P1B3
Models
without
Power
Options
P1B2
Models
with
PY Option
P1B3
Models
with
P3 and PY
Options
B014
10
16.0
16.7
16.0
16.7
16.7
14.0
4A0018
B021
15
21.9
22.6
21.9
22.6
22.6
21.0
4A0023
B027
20
33.1
33.8
33.8
33.8
33.8
27.0
4A0031
B034
25
39.4
40.1
40.1
40.1
40.1
34.0
4A0038
B040
30
47.3
48.0
48.0
48.0
48.0
40.0
4A0044
B052
40
52.7
52.7
52.7
52.7
54.0
52.0
4A0058
B065
50
65.5
65.5
64.8
64.8
66.5
65.0
4A0072
B077
60
76.7
76.7
76.0
76.7
77.6
77.0
4A0088
B096
75
99.3
99.3
98.6
99.3
100.2
96.0
4A0103
B124
100
128.1
128.1
127.4
128.1
129.1
124.0
4A0139
B156
125
162.2
162.2
162.2
162.2
163.1
156.0
4A0165
B180
150
180.6
180.6
180.6
180.6
181.5
180.0
4A0208
B240
200
239.5
239.5
239.5
239.5
241.0
240.0
4A0250
B302
250
290.1
290.1
290.1
290.1
291.6
302.0
4A0362
B361
300
346.5
346.5
346.5
347.4
347.9
361.0
B414
350
411.4
411.4
412.4
413.6
412.9
414.0
4A0414
B477
400
433.1
433.1
433.1
434.3
435.2
477.0
4A0515
B515
450
467.4
467.4
467.4
468.6
469.5
515.0
B590
500
576.7
576.7
576.7
577.9
578.8
590.0
4A0675
u
Bypass Enclosures
All P1000 Bypass units are intended for non-hazardous locations.
• P1000 Bypass units in NEMA Type 1 enclosures are constructed for indoor use to provide a degree of protection against
incidental contact with the enclosed electrical equipment and falling dust or dirt.
• P1000 Bypass units in NEMA Type 12 enclosures are constructed for indoor use to provide a degree of protection against
incidental contact with the enclosed electrical equipment, falling dust or dirt, circulating dust, dirt, lint, fibers and flyings,
and dripping at light splashing of liquids.
• P1000 Bypass units in NEMA Type 3 enclosures are constructed for indoor or outdoor use to provide a degree of protection
against incidental contact with the enclosed electrical equipment, falling dust or dirt, rain, sleet, snow, and wind-blown dust
or dirt. NEMA Type 3 enclosures will be undamaged by external formation of ice on the enclosure.
u
Bypass Product Options
Refer to Bypass Options on page 233
for details on available bypass product configuration options.
1.3 Model Numbers and Nameplate Checks
YASKAWA SIEP YAIP1B 01A YASKAWA AC Drive – P1000 Bypass Technical Manual
31
1