Yaskawa AC Drive P1000 Bypass Technical Manual User Manual
Page 326

Register No.
Contents
00D9H
oFA1x Contents (CN5)
bit 0
Option RAM Fault (oFA10)
bit 1
Option Operation Mode Fault (SLMoD) (oFA11)
bit 2
Drive Receive CRC Error (oFA12)
bit 3
Drive Receive Frame Error (oFA13)
bit 4
Drive Receive Abort Error (oFA14)
bit 5
Option Receive CRC Error (oFA15)
bit 6
Option Receive Frame Error (oFA16)
bit 7
Option Receive Abort Error (oFA17)
bit 8 to F
Reserved
00DAH
Reserved
00DBH
oFA3x Contents (CN5)
bit 0
Comm. ID Error (oFA30)
bit 1
Model Code Error (oFA31)
bit 2
Sumcheck Error (oFA32)
bit 3
Comm. option timeout waiting for response (oFA33)
bit 4
MEMOBUS Timeout (oFA34)
bit 5
Drive timeout waiting for response (oFA35)
bit 6
CI Check Error (oFA36)
bit 7
Drive timeout waiting for response (oFA37)
bit 8
Control Command Selection Error (oFA38)
bit 9
Drive timeout waiting for response (oFA39)
bit A
Control Response Selection 1 Error (oFA40)
bit B
Drive timeout waiting for response (oFA41)
bit C
Control Response Selection 2 Error (oFA42)
bit D
Control Response Selection Error (oFA43)
bit E, bit F
Reserved
00DCH to 00E9H
Reserved
00EAH
Fault Contents 9
bit 0
Time Not Set (TIM)
bit 1
Oper Battery Low (bAT)
bit 2
Time Data Err (TdE)
bit 3
Time Interval Error (TIE)
bit 4
Overvoltage 2 (ov2)
bit 5
Reserved
bit 6
External Fan Fault (Fn1)
bit 7 to F
Reserved
00EBH to 00FFH
Reserved
0100H to 2FFFH
Reserved
3000H to 3003H
Used for Various Monitors U5-oo.
Refer to U: Monitors on page 259
for details.
3004H to 3007H
Reserved
3008H to 3028H
Used for Various Monitors U2-oo, U3-oo, U5-oo.
Refer to U: Monitors on page 259
3029H to 302EH
Reserved
302FH to 83FFH
Reserved
D.9 MEMOBUS/Modbus Data Table
326
YASKAWA SIEP YAIP1B 01A YASKAWA AC Drive – P1000 Bypass Technical Manual