5 e: motor parameters – Yaskawa AC Drive P1000 Bypass Technical Manual User Manual
Page 110
Setting
Specification
Characteristic
Application
8
50 Hz, High starting torque 1
High starting torque
Select high starting torque when:
• Wiring between the drive and motor exceeds 150 m.
• A large amount of starting torque is required.
• An AC reactor is installed.
9
50 Hz, High starting torque 2
A
60 Hz, High starting torque 1
B
60 Hz, High starting torque 2
C
90 Hz (with 60 Hz base)
Constant output
Output voltage is constant when operating at greater than
60 Hz.
D
120 Hz (with 60 Hz base)
E
180 Hz (with 60 Hz base)
F
<1>
60 Hz
Variable torque
Used for variable torque applications. The default setting is
the same as V/f pattern Setting 7.
<1> Setting F enables a custom V/f pattern by changing parameters E1-05. When the bypass is shipped, the default values for parameter E1-05 is are
equal to predefined V/f pattern 1.
The following tables show details on predefined V/f patterns.
Predefined V/f Patterns for Models D002 to D024 and B001 to B011
The voltage values in the graphs for settings 0 to E apply to applications with 200 V motors. Double the voltage values for
400 V motors. The voltage values in settings 0 to E do not apply to 208, 230, or 460 V motor applications.
Table 5.10 Constant Torque Characteristics, Settings 0 to 3
Setting = 0
50 Hz
Setting = 1
60 Hz
Setting = 2
60 Hz
Setting = 3
72 Hz
0
9
200
1.3 2.5
50
15
V
oltage (V)
Frequency (Hz)
0
9
15
200
1.5 3
60
V
oltage (V)
Frequency (Hz)
0
9
15
200
1.5 3
60
50
V
oltage (V)
Frequency (Hz)
0
9
15
200
1.5 3
72
60
V
oltage (V)
Frequency (Hz)
Table 5.11 Variable Torque Characteristics, Settings 4 to 7
Setting = 4
50 Hz
Setting = 5
50 Hz
Setting = 6
60 Hz
Setting = 7
60 Hz
0
8
200
1.3
25
50
35
V
oltage (V)
Frequency (Hz)
0
9
200
1.3
25
50
50
V
oltage (V)
Frequency (Hz)
0
8
200
1.5
30
60
35
V
oltage (V)
Frequency (Hz)
0
9
200
1.5
30
60
50
V
oltage (V)
Frequency (Hz)
Table 5.12 High Starting Torque, Settings 8 to B
Setting = 8
50 Hz
Setting = 9
50 Hz
Setting = A
60 Hz
Setting = B
60 Hz
0
11
200
1.3 2.5
50
19
V
oltage (V)
Frequency (Hz)
0
13
200
1.3 2.5
50
24
V
oltage (V)
Frequency (Hz)
0
11
200
1.5 3
60
19
V
oltage (V)
Frequency (Hz)
0
15
200
1.5 3
60
24
V
oltage (V)
Frequency (Hz)
Table 5.13 Rated Output Operation, Settings C to F
Setting = C
90 Hz
Setting = D
120 Hz
Setting = E
180 Hz
Setting = F
60 Hz
0
9
15
200
1.5 3
90
60
V
oltage (V)
Frequency (Hz)
0
9
15
200
1.5 3
120
60
V
oltage (V)
Frequency (Hz)
0
9
15
200
1.5 3
180
60
V
oltage (V)
Frequency (Hz)
0
10.2
17.3
230
1.5 3
60
V
oltage (V)
Frequency (Hz)
5.5 E: Motor Parameters
110