Yaskawa AC Drive P1000 Bypass Technical Manual User Manual
Page 347

Point
No.
Point
Type
Point Name
Factory
Default
(SI Units)
Engr. Units
(SI Units)
Slope
(SI Units)
Intercept
(SI Units)
On
Text
Off
Text
Parameter
61
LAO
INPUT REF
2
0
HZ
0.01
0
–
–
d1-02
{62}
LAI
PID
FEEDBACK
0
PCT
0.01
0
–
–
U5-01
63
LAO
PID P GAIN
2
–
0.01
0
–
–
b5-02
64
LAO
PID I TIM
0.5
SEC
0.1
0
–
–
b5-03
65
LDO
PID MODE
SEL
DISABLE
–
1
0
ENABLE
DISABLE
b5-01
{66}
LAI
LST FLT
CODE
0
–
1
0
–
–
U2-02
{67}
LAI
FREF.FLT
0
HZ
0.01
0
–
–
U2-03
{68}
LAI
OUT FREQ
FLT
0
HZ
0.01
0
–
–
U2-04
{69}
LAI
OUT
CUR.FLT
0
AMPS (A)
0.01
0
–
–
U2-05
70
LAO
RD PARAM
NUM
1
–
1
0
–
–
–
71
LAI
RD PARAM
DAT
0
–
1
0
–
–
–
72
LAO
WR PARAM
NUM
1
–
1
0
–
–
–
73
LAO
WR PARAM
DAT
0
–
1
0
–
–
–
{74}
LDI
MF IN 3
MON
OFF
–
1
0
ON
OFF
UB-02 (Bit 4)
Bypass DI-5
{75}
LAI
OUT
VOLT.FLT
0
VOLTS (V)
0.1
0
–
–
U2-07
{76}
LAI
DC
BUS.FLT
0
VOLTS (V)
1
0
–
–
U2-08
{77}
LAI
OUT
PWR.FLT
0
KW
0.1
0
–
–
U2-09
{78}
LDI
MF IN 4
MON
OFF
–
1
0
ON
OFF
UB-02 (Bit 5)
Bypass DI-6
{79}
LAI
PID
DEVIATE
0
PCT
0.01
0
–
–
U5-02
80
LAO
PID I LIMIT
100
PCT
0.1
0
–
–
b5-04
81
LAO
PID UP
LIMIT
100
PCT
0.1
0
–
–
b5-06
82
LAO
PID OFFS
ADJ
100
PCT
0.1
-100
–
–
b5-07
83
LAO
PID PRI
DYTM
0
SEC
0.1
0
–
–
b5-08
84
LAO
PID FB
RMDS
0
–
1
0
–
–
b5-12
85
LAO
PID FB
RMDL
0
PCT
1
0
–
–
b5-13
86
LAO
PID FB
RMDT
1
SEC
0.1
0
–
–
b5-14
{87}
LAI
PID OUT
CAP
0
PCT
0.01
0
–
–
U5-14
{88}
LAI
PID REF
0
PCT
0.01
0
–
–
U5-04
{89}
LAI
COMM ERR
CD
0
–
1
0
–
–
U1-19
90
LDO
COMM FLT
ENA
ENABLE
–
1
0
ENABLE
DISABLE
Z3-11
91
LAO
CBL LOSS
FRQ
0
HZ
0.01
0
–
–
Z3-10
F.4 APOGEE FLN Point List Summary
YASKAWA SIEP YAIP1B 01A YASKAWA AC Drive – P1000 Bypass Technical Manual
347
F
Apogee FLN Network Protocol