Power ratings, A.1 power ratings – Yaskawa AC Drive P1000 Bypass Technical Manual User Manual
Page 224

A.1 Power Ratings
u
Three-Phase 208 Vac Bypass Drive Models D002 to D030
Table A.1 Power Ratings (Three-Phase 208 Vac)
Item
Specification
Bypass Model P1Bo
D002
D003
D004
D007
D010
D016
D024
D030
Maximum Applicable
Motor Capacity (HP)
<1>
0.5
0.75
1
2
3
5
7.5
10
Input
Input Current Range (A)
<2>
2.7
to 4.6
3.9
to 5.8
5.6
to 7.5
8.3
to 10.2
12.3
to 14.2
17.7
to 19.6
29.8
to 31.5
40.0
to 41.7
Rated Voltage
Rated Frequency
Three-phase 208 Vac 50/60 Hz
Allowable Voltage Fluctuation
-15 to 10%
Allowable Frequency
Fluctuation
±5%
Output
Rated Output Current (A)
2.4
3.5
4.6
7.5
10.6
16.7
24.2
30.8
Overload Tolerance
ND Rating: 120% of rated output current for 60 s
(Derating may be required for applications that start and stop frequently)
Carrier Frequency
<3>
User-adjustable between 2 and 15 kHz
Maximum Output Voltage (V)
Three-phase 208 Vac
Maximum Output Frequency
(Hz)
400 Hz (user-set)
<1> The motor capacity (HP) refers to a NEC rated 4-pole motor. The rated output current of the drive output amps should be equal to or greater than
the motor current. Select the appropriate capacity drive if operating the motor continuously above motor nameplate current.
<2> Assumes operation at the rated output current. Input current rating varies depending on the power supply transformer, input reactor, wiring
connections, and power supply impedance. Refer to the bypass data nameplate affixed to the inside of the enclosure door for actual input current.
<3> Carrier frequency is set to 2 kHz. Current derating is required to raise the carrier frequency.
u
Three-Phase 208 Vac Bypass Drive Models D046 to D211
Table A.2 Power Ratings (Three-Phase 208 Vac)
Item
Specification
Bypass Model P1Bo
D046
D059
D074
D088
D114
D143
D169
D211
Maximum Applicable
Motor Capacity (HP)
<1>
15
20
25
30
40
50
60
75
Input
Input Current Range (A)
<2>
56.1
to 57.8
68.9
to 70.6
89.4
to 90.3
89.5
to 92.4
113.1
to 116.0
140.2
to 142.4
165.4
to 167.6
201.4
to 203.6
Rated Voltage
Rated Frequency
Three-phase 208 Vac 50/60 Hz
Allowable Voltage Fluctuation
-15 to 10%
Allowable Frequency
Fluctuation
±5%
Output
Rated Output Current (A)
46.2
59.4
74.8
88.0
114
143
169
211
Overload Tolerance
ND Rating: 120% of rated output current for 60 s
(Derating may be required for applications that start and stop frequently)
Carrier Frequency
<3>
User-adjustable between 2 and 15 kHz
User-adjustable between
2 and 10 kHz
Maximum Output Voltage (V)
Three-phase 208 Vac
Maximum Output Frequency
(Hz)
400 Hz (user-set)
<1> The motor capacity (HP) refers to a NEC rated 4-pole motor. The rated output current of the drive output amps should be equal to or greater than
the motor current. Select the appropriate capacity drive if operating the motor continuously above motor nameplate current.
<2> Assumes operation at the rated output current. Input current rating varies depending on the power supply transformer, input reactor, wiring
connections, and power supply impedance. Refer to the bypass data nameplate affixed to the inside of the enclosure door for actual input current.
<3> Carrier frequency is set to 2 kHz. Current derating is required to raise the carrier frequency.
A.1 Power Ratings
224
YASKAWA SIEP YAIP1B 01A YASKAWA AC Drive – P1000 Bypass Technical Manual