G.1 N2 Specifications and Configuration
The bypasses can be monitored and controlled by a controller on a Metasys N2 network (N2) using RS-485 technology. The
bypass act as slaves on the N2 network.
Up to 255 bypasses can communicate on a single N2 network. If more bypasses or N2 devices are required, another N2 network
is required.
The N2 node address is configurable by a parameter in the bypass. This defines the physical address of the bypass on the N2
network.
Once the addressing is set, a controller can initiate communication to the bypass. The bypass will perform the specified function
and then send a response back to the controller.
N2
Metasys Field
Controller
P1000
Bypass
P1000
Bypass
P1000
Bypass
INCHES
D
SCALE
E
I
H
F
D
C
B
A
DATE
DATE
DATE
DATE
DATE
OF YASKAWA AMERICA INC.
WITHOUT THE EXPRESS WRITTEN CONSENT
COPIED OR DISCLOSED IN WHOLE OR IN PART
IN IT ARE CONFIDENTIAL, AND CANNOT BE
THIS DOCUMENT AND INFORMATION CONTAINED
TM
-
-
-
-
-
SEE BOM
SEE NOTES
XXX
XXX
XXX
XXX
XXX
XXX
XXX
XXX
XXXXXXX
OF
XXXXXXX
Figure G.1 Connecting Multiple Bypasses to a Metasys N2 Network
N2 specifications appear in the following table:
Item
Specifications
Interface
RS-485
Communication Parameters
Communication Speed: 9600 bps
Data Length: 8-bit (fixed)
Parity: None
Stop Bit: 1-bit (fixed)
Protocol
Metasys N2
Max Number of Drives
255 per N2 Network Segment
G.1 N2 Specifications and Configuration