Yaskawa AC Drive P1000 Bypass Technical Manual User Manual
Page 225

u
Three-Phase 208 Vac Bypass Drive Models D273 to D396
Table A.3 Power Ratings (Three-Phase 208 Vac)
Item
Specification
Bypass Model P1Bo
D273
D343
D396
Maximum Applicable
Motor Capacity (HP)
<1>
100
125
150
Input
Input Current Range (A)
<2>
284.9 to 287.1
376.8 to 380.2
450.9 to 454.2
Rated Voltage
Rated Frequency
Three-phase 208 Vac 50/60 Hz
Allowable Voltage Fluctuation
-15 to 10%
Allowable Frequency Fluctuation
±5%
Output
Rated Output Current (A)
273
343
396
Overload Tolerance
ND Rating: 120% of rated output current for 60 s
(Derating may be required for applications that start and stop frequently)
Carrier Frequency
<3>
User-adjustable between 2 and 10 kHz
Maximum Output Voltage (V)
Three-phase 208 Vac
Maximum Output Frequency (Hz)
400 Hz (user-set)
<1> The motor capacity (HP) refers to a NEC rated 4-pole motor. The rated output current of the drive output amps should be equal to or greater than
the motor current. Select the appropriate capacity drive if operating the motor continuously above motor nameplate current.
<2> Assumes operation at the rated output current. Input current rating varies depending on the power supply transformer, input reactor, wiring
connections, and power supply impedance. Refer to the bypass data nameplate affixed to the inside of the enclosure door for actual input current.
<3> Carrier frequency is set to 2 kHz. Current derating is required to raise the carrier frequency.
u
Three-Phase 480 Vac Bypass Drive Models B001 to B027
Table A.4 Power Ratings (Three-Phase 480 Vac)
Item
Specification
Bypass Model P1Bo
B001
B002
B003
B004
B007
B011
B014
B021
B027
Maximum Applicable
Motor Capacity (HP)
<1>
0.75
1
2
3
5
7.5
10
15
20
Input
Input Current Range (A)
<2>
1.6
to 2.4
2.1
to 2.9
3.6
to 4.4
5.2
to 6.1
8.1
to 9.0
13.9
to 14.7
16.0
to 16.7
21.9
to 22.6
33.1
to 33.8
Rated Voltage
Rated Frequency
Three-phase 480 Vac 50/60 Hz
Allowable Voltage
Fluctuation
-15 to 10%
Allowable Frequency
Fluctuation
±5%
Output
Rated Output Current (A)
1.6
2.1
3.4
4.8
7.6
11.0
14.0
21.0
27.0
Overload Tolerance
ND Rating: 120% of rated output current for 60 s
(Derating may be required for applications that start and stop frequently)
Carrier Frequency
<3>
User-adjustable between 2 and 15 kHz
Maximum Output Voltage (V)
Three-phase 480 Vac
Maximum Output Frequency
(Hz)
400 Hz (user-set)
<1> The motor capacity (HP) refers to a NEC rated 4-pole motor. The rated output current of the drive output amps should be equal to or greater than
the motor current. Select the appropriate capacity drive if operating the motor continuously above motor nameplate current.
<2> Assumes operation at the rated output current. Input current rating varies depending on the power supply transformer, input reactor, wiring
connections, and power supply impedance. Refer to the bypass data nameplate affixed to the inside of the enclosure door for actual input current.
<3> Carrier frequency is set to 2 kHz. Current derating is required to raise the carrier frequency.
A.1 Power Ratings
YASKAWA SIEP YAIP1B 01A YASKAWA AC Drive – P1000 Bypass Technical Manual
225
A
Specifications