B.11 o: Operator-Related Settings
The o parameters set up the digital operator displays.
u
o1: HOA Keypad Display Selection
No.
(Addr.
Hex)
Name
Description
Values
Page
o1-03
(502)
HOA Keypad Operator
Display Selection
Sets the units the drive should use to display the frequency reference and motor
speed monitors.
0: 0.01 Hz
1: 0.01% (100% = E1-04)
2: r/min (calculated using the number of motor poles setting in E2-04, E4-04,
or E5-04)
3: User-selected units (set by o1-10 and o1-11)
Default: 0
Range: 0 to 3
o1-09
(51C)
Frequency Reference
Display Units
Sets unit display for the frequency reference parameters and frequency related
monitors when o1-03 = 3.
0: WC (Inch of water)
1: PSI (Pounds per square inch)
2: GPM (Gallons per minute)
3: F (Degrees Fahrenheit)
4: CFM (Cubic feet per minute)
5: CMH (Cubic meters per hour)
6: LPH (Liters per hour)
7: LPS (Liters per second)
8: Bar (Bar)
9: Pa (Pascal)
10: C (Degrees Celsius)
11: Mtr (Meters)
12: Ft (Feet)
13: LPM (Liters per minute)
14: CMM (Cubic meters per minute)
15: “Hg (inches of mercury)
24: Custom units (determined by o1-13 to o1-15)
25: No unit
Default: 25
Range: 0 to 15; 24,
25
o1-10
(520)
User-Set Display Units
Maximum Value
These settings define the display values when o1-03 is set to 3.
o1-10 sets the display value that is equal to the maximum output frequency.
o1-11 sets the position of the decimal position.
0: No decimal point
1: One decimal point
2: Two decimal points
3: Three decimal points
Default:
<1>
Range: 1 to 60000
o1-11
(521)
User-Set Display Units
Decimal Display
Default:
<1>
Range: 0 to 3
<1> Default setting is dependent on parameter o1-03, HOA Keypad Display Selection.
u
o2: HOA Keypad Functions
No.
(Addr.
Hex)
Name
Description
Values
Page
o2-04
(508)
Drive Model Selection
Enter the drive model. Setting required only if installing a new control board. Default:
Determined by
drive capacity
u
o4: Maintenance Monitor Settings
No.
(Addr.
Hex)
Name
Description
Values
Page
o4-03
(50E)
Cooling Fan Operation Time
Setting
Sets the value of the fan operation time monitor U4-03 in units of 10 h.
Default: 0 h
Min.: 0
Max.: 9999
B.11 o: Operator-Related Settings
254