Z2: bypass control input/output – Yaskawa AC Drive P1000 Bypass Technical Manual User Manual
Page 161

No.
Name
Setting Range
Default
Z1-35
Loss of Load Bypass Output Current
0.0 to 999.9
0.0 A
n
Z1-36: Loss of Load Bypass Time
While in Bypass mode, the Loss of Load detection conditions must be met for the length of time entered here before detecting
a loss of load.
No.
Name
Setting Range
Default
Z1-36
Loss of Load Bypass Time
0.0 to 300.0
1.0 s
n
Z1-37: Set Time
Changes the LCD display to time setting to set the Real Time Clock.
No.
Name
Setting Range
Default
Z1-37
Set Time
0, 1
0
Setting 0: Normal Display
Setting 1: Displays Time and Date Setting Mode
n
Z1-38: HOA Source Select
No.
Name
Setting Range
Default
Z1-38
HOA Source Select
0 to 2
0
Setting 0: Operator
Setting 1: Digital Inputs
Setting 2: Serial Communications
n
Z1-39: Drive/Bypass Source Select
No.
Name
Setting Range
Default
Z1-39
Drive/Bypass Source Select
0 to 2
0
Setting 0: Operator
Setting 1: Digital Inputs
Setting 2: Serial Communications
n
Z1-40: Auto Transfer Wait Time
If Auto Transfer is enabled and a drive fault is detected, the bypass controller will wait the length of time entered here before
switching to bypass.
No.
Name
LCD Display
Setting
Range
Default
Z1-40
Auto Transfer Wait Time
Auto Xfer Wait T
0.0 to 300.0
0.0 s
u
Z2: Bypass Control Input/Output
n
Z2-01 to Z2-08: Digital Input 1 to 8 Function Select
No.
Name
Setting Range
Default
Z2-01
Digital Input 1 Function Select
0 to 36
21
Z2-02
Digital Input 2 Function Select
0 to 36
22
Z2-03
Digital Input 3 Function Select
0 to 36
23
Z2-04
Digital Input 4 Function Select
0 to 36
24
Z2-05
Digital Input 5 Function Select
0 to 36
25
Z2-06
Digital Input 6 Function Select
0 to 36
0
Z2-07
Digital Input 7 Function Select
0 to 36
0
5.13 Z: Bypass Parameters
YASKAWA SIEP YAIP1B 01A YASKAWA AC Drive – P1000 Bypass Technical Manual
161
5
Programming