Z3-05

(8504)

Serial Communications

Fault Select

Selects the action to take when a serial communications fault is detected.

0: Ignore. A serial communications loss will result in no action being taken.

1: Alarm only.

2: Fault with EF0.. An EF0 will be sent to the drive. If running in Bypass mode,

the bypass contactor will NOT open and the motor will keep running.

3: Fault with EF0 and Open Contactors. An EF0 fault will be sent to the drive

and the bypass contactor (K3) will be opened.

4: Alarm and run at preset speed set in Z3-10. Display AL14 alarm on

Operator.

Default: 1

Range: 0 to 4

311

Z3-06

(8505)

Serial Communications

Fault Time Select

Sets the time allowed to elapse since receiving serial communications before

triggering a communications fault.

A setting of 0.0 will never time out.

Default: 2.0 s

Min.: 0.0

Max.: 99.9

165

Z3-07

(8506)

Serial Communications

Receive to Transmit Wait

Time

Sets the time to delay a serial communications response to a serial

communications command.

Default: 5 ms

Min.: 0

Max.: 99 ms

165

Z3-08

(8507)

BACnet Device Object

Identifier 0

BACnet only.

Sets the least significant word of 22-bit virtual address.

Default: 1

Min.: 0

Max.: FFFF

165

Z3-09

(8508)

BACnet Device Object

Identifier 1

BACnet only.

Sets the most significant word of 22-bit virtual address.

Default: 0

Min.: 0

Max.: 003F

165

Z3-10

(8509)

Cable Loss Preset Frequency When a serial communications fault is detected and Z3-05=4, the resulting

value will become the frequency reference.

Default: 0

Min.: 0.0 Hz

Max.: 60.0 Hz

165

Z3-11

(850A)

Communication Fault

Detection Selection

Communication Fault Detection Selection

0: Disabled. Serial communications fault detection is completely disabled.

1: Enabled. Behavior defined by Z3-05.

Default: 1

Range: 0 to 1

165

u

Z4: Bypass Control Option Boards

No.

(Addr.

Hex)

Name

Description

Values

Page

Z4-01

(8700)

IP Address 1

Sets the most significant octet of network static IP address.

Default: 192

Range: 0 to 255

166

Z4-02

(8701)

IP Address 2

Sets the second most significant octet of network static IP address.

Default: 168

Range: 0 to 255

166

Z4-03

(8702)

IP Address 3

Sets the third most significant octet of network static IP address.

Default: 1

Range: 0 to 255

166

Z4-04

(8703)

IP Address 4

Sets the fourth most significant octet of network static IP address.

Default: 20

Range: 0 to 255

166

Z4-05

(8704)

Subnet Mask 1

Sets the most significant octet of network static subnet mask.

Default: 255

Range: 0 to 255

166

Z4-06

(8705)

Subnet Mask 2

Sets the second most significant octet of network static subnet mask.

Default: 255

Range: 0 to 255

166

Z4-07

(8706)

Subnet Mask 3

Sets the third most significant octet of network static subnet mask.

Default: 255

Range: 0 to 255

166