Yaskawa AC Drive P1000 Bypass Technical Manual User Manual
Page 185

HOA Keypad Display
Fault Name
oH3
Motor Overheat Alarm (PTC Input)
• The motor overheat signal to analog input terminals A1, A2, or A3 exceeded the alarm detection
level.
• Detection requires setting multi-function analog inputs H3-02, H3-10, or H3-06 to E.
Cause
Possible Solution
Motor has overheated
• Check the size of the load, the accel/decel times, and the cycle times.
• Decrease the load.
• Increase the acceleration and deceleration times (C1-01 and C1-02).
Adjust the preset V/f pattern. Try setting E1-03 to 6.
• Check the motor rated current.
• Enter the motor rated current to parameter E2-01 as indicated on the motor nameplate.
• Ensure the motor cooling system is operating normally.
• Repair or replace the motor cooling system.
HOA Keypad Display
Fault Name
oH4
Motor Overheat Fault (PTC Input)
• The motor overheat signal to analog input terminals A1, A2, or A3 exceeded the alarm detection
level.
• Detection requires setting multi-function analog inputs H3-02, H3-10, or H3-06 to E.
Cause
Possible Solution
Motor has overheated
• Check the size of the load, the accel/decel times, and the cycle times.
• Decrease the load.
• Increase the acceleration and deceleration times (C1-01 and C1-02).
Adjust the preset V/f pattern. Set E1-03 to 6.
• Check the motor rated current.
• Enter the motor rated current to parameter E2-01 as indicated on the motor nameplate.
• Ensure the motor cooling system is operating normally.
• Repair or replace the motor cooling system.
HOA Keypad Display
Fault Name
oL1
Motor Overload
The electronic motor overload protection tripped
Cause
Possible Solution
Load is too heavy
Reduce the load.
Cycle times are too short during acceleration and
deceleration
Increase the acceleration and deceleration times (C1-01 and C1-02).
A general-purpose motor is driven below the rated
speed with a high load
• Reduce the load.
• Increase the speed.
• If the motor is supposed to operate at low speeds, either increase the motor capacity or use a motor
specifically designed to operate in the desired speed range.
The output voltage is too high
• Adjust the V/f pattern. Set E1-03 to 6.
• Do not set E1-08 and E1-10 too low. This reduces load tolerance at low speeds.
The wrong motor rated current is set to E2-01
• Check the motor-rated current.
• Enter the motor rated current to parameter E2-01 as indicated on the motor nameplate.
The maximum output frequency is set incorrectly
• Check the rated frequency indicated on the motor nameplate.
• Set E1-03 to a V/f pattern matching the application.
Multiple motors are running off the same drive
Set L1-01 to 0 to disable the motor protection function and then install a thermal relay to each motor.
The electrical thermal protection characteristics
and motor overload characteristics do not match
• Check the motor characteristics.
• Correct the type of motor protection that has been selected (L1-01).
• Install an external thermal relay.
The electrical thermal relay is operating at the
wrong level
• Check the current rating listed on the motor nameplate.
• Check the value set for the motor rated current (E2-01).
6.4 Fault Detection
YASKAWA SIEP YAIP1B 01A YASKAWA AC Drive – P1000 Bypass Technical Manual
185
6
Diagnostics & Troubleshooting