C.1 BACnet Configuration

The P1000 Bypass system can be monitored and controlled by a controller on a Building Automation and Control network

(BACnet) using RS-485 technology and MS/TP (Master-Slave/Token-Passing) protocol. The P1000 Bypass conforms to the

BACnet application specific controller (B-ASC) device profile. BACnet MS/TP connection is made to the bypass controller.

Parameters and monitors in both the drive and the bypass controller are made accessible from this one connection.
Up to 127 bypasses can communicate on a single BACnet MS/TP network. If more bypasses or BACnet devices are required,

then a BACnet router is required to allow another MS/TP network to be available with up to another 127 bypasses.
The BACnet node address is configurable by a parameter in the P1000 Bypass. This defines the physical address of the bypass

on the MS/TP network. In addition, both the Device Object instance ID and the Device Object Name are configurable. These

allow the bypass to have a virtual address, and simplify the controller configuration.
Once the addressing is set, a controller can initiate communication to the P1000 Bypass. The bypass will perform the specified

function and then send a response back to the controller. The bypass will usually respond immediately, but may delay its

response until it gets the token for commands that may take extra local processing time.

BACnet

Workstation

MS/TP

BACnet over Ethernet

Router

Router

P1000

Bypass

P1000

Bypass

P1000

Bypass

P1000

Bypass

P1000

Bypass

P1000

Bypass

INCHES

D

SCALE

E

I

H

F

D

C

B

A

DATE

DATE

DATE

DATE

DATE

OF YASKAWA AMERICA INC.

WITHOUT THE EXPRESS WRITTEN CONSENT

COPIED OR DISCLOSED IN WHOLE OR IN PART

IN IT ARE CONFIDENTIAL, AND CANNOT BE

THIS DOCUMENT AND INFORMATION CONTAINED

TM

-

-

-

-

-

SEE BOM

SEE NOTES

XXX

XXX

XXX

XXX

XXX

XXX

XXX

XXX

XXXXXXX

OF

XXXXXXX

MS/TP

Figure C.1 Connecting Multiple P1000 Bypasses to a BACnet Workstation

C.1 BACnet Configuration

288

YASKAWA SIEP YAIP1B 01A YASKAWA AC Drive – P1000 Bypass Technical Manual