Bypass control board leds, Alarm (alm) led displays, Auto led and hand led indications – Yaskawa AC Drive P1000 Bypass Technical Manual User Manual
Page 62: For details

u
Bypass Control Board LEDs
The bypass control board A2 has six bi-color LEDs.
The operational states of the bypass LEDs after completion of the power-up diagnostic LED sequence are described in
Table 4.2 Bypass Control Board LED States
Name
Description
Color
Behavior
MS
Module Status
Red
Not used
Green
Turns ON when transmitting
Turns OFF when receiving
NS
Network Status
Red
Not used
Green
Turns ON when transmitting
Turns OFF when receiving
ST1
ST1, Status 1
Red
Not used
Green
Round status
Toggles ON/OFF every 500 rounds
ST2
ST2, Status 2
Red
Not used
Green
Scan status
Toggles ON/OFF every 500 scans
ST3
ST3, Status 3
Red
Not used
Green
Not used
ST4
ST4, Status 4
Red
Not used
Green
Not used
u
ALARM (ALM) LED Displays
Table 4.3 ALARM (ALM) LED Status and Contents
State
Content
Display
Illuminated
When the drive detects an alarm or error.
Flashing
• When an alarm occurs.
• When an oPE is detected.
• When a fault or error occurs during Auto-Tuning.
Off
Normal operation (no fault or alarm).
u
AUTO LED and HAND LED Indications
Table 4.4 AUTO LED and HAND LED Indications
AUTO LED
HAND LED
State
AUTO
Off
HAND
Off
OFF mode
AUTO
Off
HAND
On solid
HAND mode
AUTO
Off
HAND
Long blink (50% duty)
HAND mode when the Frequency Reference is 0 and/or decelerating in HAND mode.
AUTO
On solid
HAND
Off
Running in AUTO mode
AUTO
Long blink (50% duty)
HAND
Off
Running in AUTO mode when the Frequency Reference is 0 and/or decelerating in AUTO
mode.
4.2 Using the HOA Keypad
62
YASKAWA SIEP YAIP1B 01A YASKAWA AC Drive – P1000 Bypass Technical Manual